TDK-Lambda Alpha 1000 Handbook Download Page 18

 

 

 

Page 18 of 29 

 

 

 

17027 issue 23, June 2014 

 

 

 

 

 

 

 

 

 

    

    

 

Alpha 1000 Handbook

 

 

(a)  C modules can be used up to 16A for outputs up to 12V.  For 15-16V outputs C modules can be used at up 

to 12A.  
        Maximum module output current derates linearly between 12V and 15V. 

 

(b)  C modules can be used up to 10A in slot 7 and up to 16A in all other slots, subject to the limitations of (a). 

D modules can be used at up to 8A in slots 1-6. In slot 7 this reduces to 5A. 

 

E modules can be used up to 5A in slot 7 and up to 8A in all other slots. 

 

EQ and EB modules can be used up to 5.6A in slot 7 and up to 9A in all other slots. 

 

F modules can be used up to 20A in slots 6 and 7 and up to 33A in all other slots. 

 

G modules can be used up to 15A in slots 6 and 7 and up to 25A in all other slots. 

 

H modules can be used up to 3A in slot 7 and up to 5A in all other slots.  For 29.01 - 32V output current is limited 

to 1A max for all slots. 

 

J modules can be used up to 6A in slots 6 and 7 (for 30-48V).  For all other slots the max. permitted current is 

limited to 8A at   48V and 10A at 41V.  For intermediate voltages interpolation is used to determine the max. 
permitted current.  For outputs in the range 36-41V max. current is 10A. 

 

K modules can be used up to 10A in slot 6/7 and up to 15A in all other slots. 

 

L modules can be used up to 15A in slot 7 and used up to 25A in all other slots. 

 

M modules can be used up to 5A in slot 7 and up to 8A in all other slots. 

 

(a)  N modules can be used up to 5A for outputs up to 29V.  For 29-32V output current is limited to 1A max. 

 

(b)  N modules can be used up to 3A in slot 7 and up to 5A in all other slots.   

 

P modules can be used up to 5A on the 18-29V channel in slots 1 to 6 and up to 3A in slot 7. 

 

P modules can be used up to 8A in the 5-16V channel in slots 1 to 6 and up to 5A in slot 7. 

 

Q modules can be used up to 25A in slots 1-6. In slot 7, this is 15A. 

 

R modules can be used up to 60A in any slot. 

 

S modules can be used up to 75A in slots 1/2,  76A in slots 2/3; 51A in slots 6/7 and up to 85A in all other slots.  

When the psu is operated in a horizontal orientation (with the ratings label uppermost) the S modules may be used 
up to 85A in slots 2/3. 

 

T modules can be used up to 37A in slot 6 and 7 and used up to 60A in all other slots. 

 

U modules can be used up to 16A in all slots. 

 

W modules can be used up to 15A in all slots. 

 

Z modules can be used up to 15A in slot 7 and used up to 25A in all other slots. 

 
Additional module limitations: 

 
When using remote sense, the max output voltage will be reduced by 0.5V for L, S, T, Q and R modules, and  
by 1.0V for C, D, F, G, J, M, K, N, U Modules. 
Ampere turns for J module is calculated as AT=(output c 15A) x 4. 
Adjusting output voltage beyond the stated range may cause overvoltage protection (OVP) to operate, whereby all 
outputs will turn off. To reset OVP, turn back output voltage adjustment and remove the mains supply for 30 
seconds. 
 

Input Connections:   
 

Mating input faston connectors 

Brand 

Colour 

Wire size (awg) 

Part number 

Current rating 

Amp 

Red 

22 - 18 

2-520407-2 

15A 

Amp 

Blue 

16 - 14 

3-520408-2 

15A 

 

 
 
 
Output Connections: 

 
Output Connector Ratings: 
 

1.  6.35mm fastons are rated at 15A. 
2.  9.5mm Faston terminals are rated at 32A (Tab thickness = 1.0mm, suitable Faston terminals are AMP 

151667-2 or AMP 280223-2 

3.  M5 screw terminals are rated at 100A subject to the wire and wire connector used to connect them. 

 
 Maximum recommended torque setting for M5 screws is 2.4 – 2.6Nm. 
 

Summary of Contents for Alpha 1000

Page 1: ...el except as stated in the product limitations in this handbook Input Parameters This product must be operated within the input parameters stated in the product limitations in this handbook End of Lif...

Page 2: ...tent contact with these module output terminals If set such that hazardous energy can occur then the module terminals or connections must not be user accessible HOT SURFACE External Hot Surfaces In ac...

Page 3: ...in den Produktgrenzen dieses Handbuches ausgezeichnet ist Eingangsparameter Dieses Produkt muss innerhalb der Eingangsparameter die in den Produktgrenzen dieses Handbuches angegeben sind betrieben we...

Page 4: ...r Servicepersonal vor unbeabsichtigtem Kontakt mit den Ausgangsanschl ssen dieser Module vorsehen Kann aufgrund der Einstellung gef hrliche elektrische Energie auftreten d rfen die Modulanschl sse f r...

Page 5: ...l intensit nominale marqu e sur la plaque signal tique sauf indications contraires dans les limitations du produit d crit dans ce manuel Param tres d entr e Ce produit doit tre utilis l int rieur des...

Page 6: ...ension de sortie Le fabricant de l quipement final doit assurer la protection des techniciens d entretien contre un contact involontaire avec les bornes de sortie de ces modules Si une telle tension d...

Page 7: ...vratensione II Questo prodotto contiene schede di circuiti stampati in materiali di Gruppo IIIb Carico in uscita La potenza in uscita ottenuta dall alimentatore non deve superare la potenza nominale i...

Page 8: ...rogare energia pericolosa 240 VA a seconda della tensione in uscita impostata I produttori delle apparecchiature finali sono tenuti a proteggere il personale di manutenzione dal rischio di contatto ac...

Page 9: ...utilizan policloruros de bifenilo del Grupo de materiales IIIb Carga de salida La potencia de salida tomada de la fuente de alimentaci n no puede sobrepasar el valor nominal indicado en la etiqueta de...

Page 10: ...eden generar energ a peligrosa 240VA dependiendo de la configuraci n de la tensi n de salida Los fabricantes de equipos finales deben proteger al personal de servicio contra un contacto accidental con...

Page 11: ...retens o II S o utilizadas placas de circuitos impressos do grupo de materiais IIIb Carga de sa da A pot ncia de sa da extra da da fonte de alimenta o n o deve exceder a classifica o assinalada na eti...

Page 12: ...energia perigosa 240 VA de acordo com a configura o da tens o de sa da O equipamento final do fabricante deve garantir que o pessoal de assist ncia est protegido contra contactos inadvertidos com est...

Page 13: ...water IPX0 Reference should be made to local regulations concerning the disposal of these products at the end of their useful life Where any part of this product is made accessible to the operator in...

Page 14: ...uration Code Alpha 1000 and CA1000 are identical Alpha 1000 or CA1000 may be followed by TL RL LL or ML Where TL Tiny leakage input filter RL Reduced leakage input filter LL Low leakage input filter M...

Page 15: ...ules providing a max output of up to 16V only or b Identical to _PA except that the module is paralleled at the output of the module with busbar linking _IN Provides an external signal which may be us...

Page 16: ...vertical with airflow downwards Model CA1250 12C_MF 12FF 12FF 12FF NS AMD 005 Input voltage range 207 264Vac Outputs C Module 13V max 16A max F Module 13V max 30A max F Module 13V max 30A max F Modul...

Page 17: ...ing for Hazardous Energy A 4 5 5 5V 60A 2 1 60 79 2A 3V AA 4 5 6 2V 60A 2 1 60 79 2A 3V B 4 5 5 5V 25A 1 1 25 33A BB 4 5 6 5V 25A 1 1 25 33A C 5 16V 16A 1 2 32 21 2A 11 3V D 18 29V 8A 1 4 32 10 6A 22...

Page 18: ...les can be used up to 5A on the 18 29V channel in slots 1 to 6 and up to 3A in slot 7 P modules can be used up to 8A in the 5 16V channel in slots 1 to 6 and up to 5A in slot 7 Q modules can be used u...

Page 19: ...be used to ensure the PSU is operated within its ratings 1 Calculate the output power for each module Volts x Amps 2 Total power for slots 1 3 must be 720W Total power for slots 4 7 must be 600W Total...

Page 20: ...Page 20 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Main Base PCB...

Page 21: ...Page 21 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Forward Converter No 1 Forward Converter No 2...

Page 22: ...Page 22 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Single Module PCB Dual Module PCB...

Page 23: ...Page 23 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Twin Module PCB J Module PCB...

Page 24: ...Page 24 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook L Module PCB S Module PCB...

Page 25: ...Page 25 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook T Module PCB MF Option MFV Option...

Page 26: ...Page 26 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook...

Page 27: ...n PP Parrallel Connector Six way Molex 90142 0006 Crimp terminals 90119 2109 MF MFL MFE MFU MFV Pin 1 Inhibit Low Enable Low Inhibit Low Inhibit Low Pin 2 5V Aux 5V Aux 5V Aux 5V Aux Pin 3 Power Fail...

Page 28: ...119 2109 Crimp terminals 90119 2109 1 ve sense 2 Module Good 3 Star Point 4 ve sense 5 ve power 6 Star Point Option RP Remote Programming Module Positions 1 Not connected 2 Module Good 3 Inhibit input...

Page 29: ...Alpha 1000 Handbook Customer fixings TDK Lambda UK Ltd Kingsley Avenue Ilfracombe Devon EX34 8ES Telephone Sales and Service 44 0 1271 856666 Head Of ce and Works 44 0 1271 856600 Facsimile 44 0 1271...

Reviews: