background image

2800 Laura Lane • Madison, WI 53562  |  800.288.9383 • fax: 608.836.9044  |  www.tcsbasys.com  

5

Once you have made connection and have logged in you are able to configure the operation of the unit by selecting the 

proper parameters for your application . All Ubiquity

 

Cloud application software and functionality is accessed by logging 

into the central server (www .ubiquitysystems .net) not by using this configuration page . 

INSTALLATION INFORMATION

This section contains installer and site related 

information . The information entered here is sent to the 

central server when a site initially comes online to help 

identify the site to link it to the correct Ubiquity site . For 

the most part, this information is for reference purposes 

only, except for the Site Time . The Site Time is used by 

the local network and the QD2040b until the Ubiquity 

central server performs a time synchronization with the 

site . 

NOTE

: Be sure to set the correct Time zone so that the 

site will correctly adjust the time during future time 

synchronizations with the central server . 
Once you are finished entering information in this 

section,click the Update Installation Info button .

APPLICATION INFORMATION

This section contains settings which define how the 

QD2040b interacts with the controller network, and how 

it communicates the data to the actual server . 

Application Options: 

You must select a Network Polling 

Cycle Time for the QD2040b . This is the time interval 

that the unit will poll the entire network of controllers 

on all ports . The default setting is 1 minute . You must 

select whether or not to allow caching the host name via 

DNS . Typically, this is left unchecked . You must select 

how often the QD2040b connects to the central server . 

Typically this is set to “Always On .”

RS-485 Network

 - Port Configuration: Here you will 

configure each of the COM ports for this site . Typically, 

you will leave Auto Detection of Controls on All Ports  

enabled so the QD2040b will find and add the controller 

as they are included on one of the networks (wired or 

wireless) . If disabled, new controllers must be added 

manually in Ubiquity .
The communication ports are automatically detected 

once the QD2040b is powered up . Once detected each 

COM port needs to be configured to ensure proper 

functioning of the network on each port . Each port can 

be enabled or disabled from the drop down menu .
You must also select the proper protocol being used 

on each port . The current protocol selections from the 

drop down menu are TCSbus or Modbus . You must also 

select the communication baud rate for each port . This 

setting must be the same as all of the controllers on 

that port . You can also adjust the Time-Out Period for 

each port . TCS recommends 250ms for wired networks 

and 1000ms for all wireless networks . 

GATEWAY 

CONFIGURATION

Gateway Configuration Page

Summary of Contents for Ubiquity QD2040b

Page 1: ...WI 53562 800 836 9044 fax 608 836 9044 www tcsbasys com Rev 0617 The QD2040b Ubiquity Cloud Site Gateway connects the site controller network with the Ubiquity Cloud server QD2040b Ubiquity Cloud Site...

Page 2: ...tines Supervisory override strategy Auto discovery of networked controllers Two integrated RS 485 serial ports Additional serial ports can be added via USB ports Integrated Ethernet controller with fi...

Page 3: ...er QD1010 or connect a TCS ZigBee network via a wireless gateway QW1010 Refer to RS 485 Controller Network Wiring Setup below Power Attach the included power supply to the back unit and insert the pow...

Page 4: ...wiring to earth ground TCS recommends a 250 milliseconds time out period for all wired networks and 1000 milliseconds for wireless networks If you encounter timeout errors please contact tech support...

Page 5: ...a to the actual server Application Options You must select a Network Polling Cycle Time for the QD2040b This is the time interval that the unit will poll the entire network of controllers on all ports...

Page 6: ...o be used When using static IP it is necessary to enter the IP Address Gateway Subnet DNS1 and DNS2 settings Virtual IP can be used typically left blank The IP settings will need to be established by...

Page 7: ...ser interface at this point Clicking the green button with the arrow on it on the right side of the Ubiquity Connection Status title bar will refresh the connection status COMMISSIONING TOOLS Commissi...

Page 8: ...the network must have a unique address excluding the reserved address 248 Network wiring should also be checked The LEDs on the QD2040b indicate the current operating status of the QD2040b POWER This...

Reviews: