COMISSIONING

 

& PROGRAMMING

AI1 AMBIENT LIGHT INPUT

If using an ambient light sensor (0 to 5 or 1 to 5V); set the 

low and high scaling limits for AI2 . These limits are what 

the light sensor reads at low limit and what the light sensor 

reads at full scale .

A Lighting Channel Threshold and Hysteresis for each of 

the available channels can be set for this input signal. The 

Channel Power Threshold is basically a setpoint for which 

AI1 is compared to determined when to turn off the select-

ed cycle(s). The Channel Power Hysteresis is a buffer value 

which is prevents the channel from cycling off/on prema-

turely. For example, if the input is scaled 0 to 1000 lumens 

and you want to turn off one channel if the input gets up to 

500 lumens and allow it to come back on if the input falls 

to 400 lumens, enter in 0 for the scaling low limit, 1000 for 

the scaling high limit, 500 for the threshold and 10% for the 

hysteresis for that channel . 
Select a threshold and hysteresis for the channels which 

will be allowed to be shut off based on this input hitting the 

threshold . A common application for this feature is to con-

trol parking and exterior signage lighting . Essentially the 

channel will be on all the time it is occupied except when 

there is too much light . (Similar to the astronomical time 

function).  If AI1 is not used, the threshold for all channels 

MUST equal the scaling high limit.

AI2 ENERGY / POWER / MONITORING INPUT

If using an energy meter, power meter or current trans

-

ducer (0-5V), set the low and high scaling limits for AI2. 

These limits are what the energy or power meter reads at 

0V and what the energy or power meter reads at 5V . For a 

4 to 20mA input to be wired to AI2, a 250 Ω resistor must 

be installed between AI2 and GND. If you want to use this 

input with a threshold and hysteresis (Channel Power 

section) to shut off lighting channels, select the relevant 

lighting channels (Enable AI2 Threshold checkboxes) and 

enter a threshold and a hysteresis to be used. If AI1 is not 

used, the channel power threshold MUST equal the scaling 

high limit .
Select whether you want the time clock output (Digital 

Output Mode) to be Normally Open or Normally Closed dur

-

ing on periods .

The Channel Power Threshold is basically a setpoint to 

which AI2 is compared to determine when to turn off the 

selected channel(s). The Channel Power Hysteresis is a 

buffer value which prevents the channel from cycling off/

on prematurely. For example, if the AI2 input is scaled 0 to 

10000 KW and you want to turn off some channels if the 

input gets to 7500 KW and allow them to come back on 

if the input falls to 6500 KW, enter in 0 for the scaling low 

limit, 10000 for the scaling high limit, 7500 for the thresh

-

old and 10% for the hysteresis. You should choose this 

threshold to be larger than the accuracy/error specification 

of the equipment/device being turned off so it does not 

cycle on and off .

AI2 AMBIENT LIGHT INPUT

If AI2 is not used for power limiting, a second light sensor 

can be used to monitor another area. Set the low and high 

limits for AI2 . These limits are the light sensor reading at 

0Vand the sensor reading at 5V respectively . Click on the 

Enable box for each of the channels to be controlled by 

AI2 (in the Enable AI2 as Light Level Source column). Then 

proceed to enter threshold and hysteresis values for each 

channel (located just below the AI1 AMBIENT LIGHT INPUT 

section). Each channel that is selected/checked (Enable 

AI2 as Light Level Source) will then have its threshold/hys-

teresis compared to AI2 instead of AI1 .

CHANNEL MONITORING AND CONTROL

DI1 and Override 1 are used for Channel 1, DI2 and Override 

2 are used for Channel 2, etc.

 

There are four Digital Input Modes which can be used with 

a digital input: Regular, External Override, Momentary Over

-

ride, & Monitor.

Regular mode:

 The digital input is used in conjunction with 

the programmed schedule in determining when the relay 

output should be on or off.

External Override mode:

 The digital input acts the same as 

the override button on the front of the QWL 3.1 Rev 3 Series 

Summary of Contents for QWL 3.1 Rev 3

Page 1: ...x 608 836 9044 www tcsbasys com Rev 0617 PRODUCT MANUAL The QWL 3 1 Rev 3 Integrated Building Manager Panel contains a Ubiquity Cloud Site Gateway w integrated lighting and energy management controls...

Page 2: ...METER SEQ100 Utility Pulse Counting Meter for Monitoring of Electric single and 3 phase kW and kWh Gas Water BT LIGHTING CONTROLLER SLQ218 365 day programming for each circuit Analog input for photo...

Page 3: ...y contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 3 SERIES PANEL The QWL 3 1 Rev 3 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3...

Page 4: ...wire a 120 terminating resis tor across the A and B terminals at the QWL 3 1 Rev 3 Series Panel See 1 below If the QWL 3 1 Rev 3 Series Panel will be in the middle of the network do not wire in the te...

Page 5: ...ormation in this section click the Update Installation Info button RS 485 Network Port Configuration Configure each of the detected COM ports for this site Typically you will leave Auto Detection of C...

Page 6: ...ng Info button SECURITY INFORMATION This section contains settings which control the security of the gateway within the QWL 3 1 Rev 3 Series Panel and whether or not it can be accessed through the web...

Page 7: ...must be programed using TCS Insight or Ubiquity Cloud CHANNEL EVENT SCHEDULING There are eight independent channels each with its own schedule If the occupied or ON time for a particular day is from...

Page 8: ...ng channels Enable AI2 Threshold checkboxes and enter a threshold and a hysteresis to be used If AI1 is not used the channel power threshold MUST equal the scaling high limit Select whether you want t...

Page 9: ...cal time calculation Next select the channel s that should have the astronom ical time function and click the Enable box This is done in the Schedule section of the page Note For non North American Da...

Page 10: ...CT or on the utility output meter This value is only used for and electric meter P REV The Pulses per revolution for the meter This value is usually provided from the utility company CONSTANT The val...

Page 11: ...e to check and verify all wiring before powering up the QWL 3 1 Rev 3 Series Panel The QWL 3 1 Rev 3 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or great...

Page 12: ...rify that the power supply nodule included with the QWL 3 1 Rev 3 Series Panel is plugged in to an outlet that has power IF THEN Check that the baud rate set on the controller s are all set the same V...

Reviews: