background image

 

11/2012 

TCS TürControlSysteme AG, TCS Hotline Germany:  +49 (0) 41 94/ 9 88 11 88

 

Subject to technical changes. 

FAX: +49 (0) 41 94/ 9 88 129  

  Mail: [email protected]

 

PI_PUK-uk   1 A 

 

Table of contents 

 

Scope of delivery ................................................................................................................. 3

 

Safety instructions................................................................................................................ 3

 

General safety regulations ............................................................................................... 3

 

Installation 

– protective measures .................................................................................... 3

 

Intended use ........................................................................................................................ 3

 

Device overview PUK .......................................................................................................... 4

 

Technical data ..................................................................................................................... 4

 

Short description .................................................................................................................. 5

 

win:clip system ..................................................................................................................... 5

 

Installation ............................................................................................................................ 6

 

Notes ................................................................................................................................ 6

 

Flush-mount box ........................................................................................................... 6

 

Front-door station ......................................................................................................... 6

 

Connecting the lines ............................................................................................................ 6

 

General information .......................................................................................................... 6

 

Connecting ....................................................................................................................... 6

 

Connecting with a screw terminal with 5 poles ................................................................. 6

 

Wiring example................................................................................................................. 7

 

2-wire special operation ................................................................................................... 7

 

Commissioning .................................................................................................................... 7

 

Adjusting the volume of microphone and loudspeaker......................................................... 8

 

Labelling the name tags ....................................................................................................... 8

 

Bell button programming ...................................................................................................... 9

 

Basic principle .................................................................................................................. 9

 

Programming a bell button ............................................................................................... 9

 

Programming a second indoor station at a bell button (parallel call) .............................. 11

 

Delete the programming ................................................................................................. 12

 

General information on the conduit in TCS audio systems ................................................ 13

 

Principle loop resistance ............................................................................................. 13

 

Measure loop resistance ............................................................................................. 13

 

Repair ................................................................................................................................ 14

 

Replace the EEPROM storage ....................................................................................... 14

 

Cleaning ............................................................................................................................. 14

 

Conformity ......................................................................................................................... 15

 

Information on disposal ...................................................................................................... 15

 

Warranty ............................................................................................................................ 15

 

Accessory .......................................................................................................................... 15

 

Service ............................................................................................................................... 16

 

 
 
 
 
 
 
 
 
 

Summary of Contents for PUK Series

Page 1: ...trolSysteme AG TCS Hotline Germany 49 0 9 41 94 9 88 11 88 Subject to technical changes FAX 49 0 41 94 9 88 129 Mail info tcsag de PI_PUK uk 1 A Product Information Front door station series for flush...

Page 2: ...ng the lines 6 General information 6 Connecting 6 Connecting with a screw terminal with 5 poles 6 Wiring example 7 2 wire special operation 7 Commissioning 7 Adjusting the volume of microphone and lou...

Page 3: ...cording to DIN VDE 0100 must be observed When installating TCS BUS systems the general safety regulations for telecommunication systems according to VDE 0800 must be observed Inter alia separated cond...

Page 4: ...re 20 C 50 C input current PUKxx 1 I a 0 4 mA I P 19 mA stand by PUKxx 2 I a 0 8 mA I P 36 mA PUKxx 3 I a 1 2 mA I P 53 mA max input current PUKxx 1 I Pmax 36 mA PUKxx 2 I Pmax 40 mA PUKxx 3 I Pmax 58...

Page 5: ...to connect an extended function door release door release time at R terminal ex works 3 sec can be adjusted with configo TM door standby time to control the short term memory within the indoor statio...

Page 6: ...glass Do not under any circumstances seal the device with silicone Condensed water must be able to run and evaporate Connecting the lines General information Connect the lines with the enclosed small...

Page 7: ...e the R terminal to connect a door release relay 2 wire special operation In this operation mode only one front door station can be connected One P wire is to be build by a jumper between terminal a a...

Page 8: ...ume at the front door station Labelling the name tags Please find the templates under www tcsag de Downloads Produktnutzung Vorlagen f r Namensschildbeschriftungen Namensschildbeschrif tung Au enstati...

Page 9: ...l number condition ex works allocation de leted this button can be used to switch lights Programming a bell button Make sure that the indoor station is connected to the TCS BUS and the mains voltage i...

Page 10: ...door and indoor station 1 2b Alternatively programming via floor push button if the indoor station is not accessible Press floor push button 2 times in quick succession each time a ring tone sounds p...

Page 11: ...nfigo TM Note Repeated programming of an already programmed bell button always changes only the second serial number If you want to change the serial number programmed first you have to delete both se...

Page 12: ...he configuration software configo TM Delete the programming Before an already programmed bell button can be reprogrammed the previous program ming must be deleted 1 Initiate Power supply and control u...

Page 13: ...lded lines connect the shields with each other and connect one side to ground b wire at the power supply optional strand or star formed wiring Table loop resistances cable length in m cable diameter 0...

Page 14: ...nt door station and inserted into a new identical constructed front door station Before replacing the EEPROM switch off the supply voltages Note Every front door station of the serien PUK is fitted wi...

Page 15: ...isposed separateley from domestic waste The materials used are recyclable Please do help protecting out environment and dispose the device via a collection point for electronic scrap Dispose the parts...

Page 16: ...ect to technical changes FAX 49 0 41 94 9 88 129 Mail info tcsag de PI_PUK uk 1 A Service Please send your questions and inquiries to hotline tcsag de Headquarters TCS T rControlSysteme AG Geschwister...

Reviews: