        Communicating Thermostats

        Communicating Thermostats

SZ1061/SZ1062

Digital Fan Coil Thermostats

Product Manual           

Description                              

The SZ1062 is a microprocessor based programmable 

digital fan coil controller and the SZ1061 is a non-pro-

grammable digital fan coil thermostat

Features                                 

•  Stand-alone or network operation 

•  P+I control option

•  No battery backup required

•  Minimum on/off times for HVAC equipment protection

•  32-character LCD display

•  Six status LEDs 

•  Remote room sensing capability

•  User setpoint adjustment limits

•  Three speed fan

•  System and fan switching with access lockouts

•  External input for setback or aquastat changeover

•  Access to programming may be locked out or limited 

with the use of an access code

•  Fahrenheit or Celsius temperature display

•  Control for two or four pipe systems

•  7-day programmable time clock

•  Optional pipe sensor inputs for changeover          

(SZ1062 only) 

•  Adjustable delay on start-up and power-up for soft 

starts

•  Smart recovery (SZ1062 only) 

•  Local and remote override capability

•  External time clock and override options

•  Auxiliary output for heat, cool or time clock (SZ1062 

only) 

Contents                                 

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Sequence of Operation

  . . . . . . . . . . . . . . . . . . . . . . . .

6

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . .

8

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

Mounting                                  

The SZ1061 and SZ1062 are designed for wall mounting 

using two #6 sheet metal screws, either over a horizon-

tally installed 2" x 4" junction box, or directly to block or 

drywall.
For best results, the thermostat should be mounted on 

an interior wall which reflects normal room environment, 

at a height of approximately five feet from the floor. 

Avoid areas exposed to direct sunlight, unusual heat or 

cool sources, open doors and windows, unventilated 

locations and hot or cold air from diffusers.
If using a remote room sensor, it should be mounted in 

the manner described above. The thermostat may then 

be mounted in an area which is accessible for adjusting 

its settings.

Caution:  Remove power from thermostat prior to 

mounting.

SZ1061 has been discontinued January 2013

Summary of Contents for SZ1061

Page 1: ...Z1062 only Adjustable delay on start up and power up for soft starts Smart recovery SZ1062 only Local and remote override capability External time clock and override options Auxiliary output for heat...

Page 2: ...using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone...

Page 3: ...through the PC consult your TCS software manual PROGRAMMING THROUGH THE KEYPAD To access the programming screens press the program setup button Screens A thru F are monitoring screens and programming...

Page 4: ...to two occupied periods SZ1062 only Schedule Announcement Screen Announces the next screen SZ1062 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the...

Page 5: ...tput a stage of HEAT or a stage of COOL SZ1062 only Time Clock Output Screen Choose whether the auxiliary output will be OPEN or CLOSED during occupied periods This screen is not used if step 29 is se...

Page 6: ...ime remaining elapses they may press the override button again Additionally an Override Hold feature is built into the thermostats When in unoccupied mode pressing the override once and then pressing...

Page 7: ...em See setup instructions for dipswitch placement for this option The pipe temperature span is 0 to 150 F 17 8 to 65 6 C DIGITAL OUTPUTS The digital outputs on the SZ1061 and SZ1062 are used to contro...

Page 8: ...NOTE The fan has a minimum on and off time of 30 seconds A relay for heating or cooling has a minimum on and off time of 2 minutes NOTE The SZ1061 does not show the day or time 2 Turn power on The th...

Page 9: ...If any of the temperatures are still reading slightly high or low you can add in a temperature offset calibration using Ubiquity or TCS Insight In Ubiquity you can edit the calibration off set for eac...

Page 10: ...80 minutes This value may be changed from 0 to 255 minutes in programming step 23 SETTING CLOCK SCHEDULE The ability to set the clock and schedule is allowed by factory default An access code may be r...

Reviews: