2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
2
Wiring
The SZ1061 and SZ1062 use standard terminal desig-
nations for wiring. See diagram below.
REMOTE SENSOR WIRING
The SZ1061 accepts one 1000 ohm two-wire platinum
sensor and the SZ1062 accepts two. Use TS1009,
TS1002 with TQ Series Immersion wells or TS1005 for
water temperature sensing.
When using TCS/Basys Controls three-wire sensors,
use the black and red leads, and either clip or twist off
the white lead. The wiring length should not exceed
250 ft.
POWERING THE SZ1061 &SZ1062
Superstats are powered from 24 VAC +/- 20%.
If wiring for communications, dedicated power must be
used to power the Superstat. Several “S” Series thermo-
stats may be powered from the same transformer, pro-
vided that the transformer has sufficient power.
(Superstats require 8 VA @ 24 VAC.)
Caution:
Do not connect to 120 VAC. When multiple
TCS/Basys Controls devices are using a single
transformer, the polarity of the power wiring
must be maintained because all TCS devices
are half-wave rectified and have common
return paths.
When the Superstat is used as a stand-alone thermostat
without communications, the unit transformer may be
used to power it. To do this, install a jumper between the
“R” and “+24” terminals. The “24-” terminal must then
be connected to the common side of the unit transform-
er.
Setup
Black
1
For communication wiring, use twisted,
shielded 18 AWG.Must be run separately.
2
Dry momentary contct. Must not be
powered.
3
24 VAC transformer. See powering
instructions.
4
5
Sensor input wiring 18 AWG, twisted, shielded pair.
Dry contact. Must not be powered.
6
3
4
4
4
5
5
Remote
Zone/Return
Air Temp
Pipe
Temp
2
REF A B
Up to nominal 28 VAC from equipment transformer.
Black
Red
Red
Input Wiring for the SZ1061 and SZ1062
A
B
R
1
6
REF
REF A B
Y1
R W1 Y1
W1
G
Med
G
Hi
Aux. Relay
Output
G
Low
GL GM GH
R2 A1
Output Wiring for the SZ1061 and SZ1062
* When heating and cooling on
a two-pipe unit, use Y1
** When heating only on a
two-pipe unit, use W1
*** When cooling only on a
two-pipe unit, use Y1
*
***
**