In programming screen #44, you are asked to enter 

a reset ratio factor. This  is the number of degrees 

that the discharge air setpoint is raised when the 

room temperature falls below the heating setpoint by 

1 degree if the analog output is set for heating, or the 

number of degrees that the discharge air setpoint is 

lowered when the room temperature rises above the 

cooling setpoint by 1 degree if the analog output is set 

for cooling.

OUTDOOR AIR TEMPERATURE SENSING

The  SZ1018 accept a remote 1000 

 outdoor tem-

perature sensor (TS1003) for monitoring purposes. 

(See setup instructions for dipswitch placement for 

this option.) 
Choose YES in programming screen #45 only if you 

are using an outdoor air sensor and you want to 

enable the outdoor air heating and cooling lockout 

functions (Do not use with Zoning System). If NO is 

chosen, the outdoor air is still monitored. 
When the function is enabled, a COOLING LOCKOUT 

TEMP and HEATING LOCKOUT TEMP are entered 

in steps #46 and #47. If the outdoor temperature falls 

below the COOLING LOCKOUT TEMP, all cooling 

stages will be locked out and will remain locked out 

until the outdoor air temperature rises 2° above the 

lockout temperature. If the outdoor temperature rises 

above the HEATING LOCKOUT TEMP, all heating 

stages will be locked out and will remain locked out 

until the outdoor air temperature falls 2° below the 

lockout temperature. 
The outdoor air span is -40 to 160 °F (-40.0 to 71.1 

°C).

FAN PROVING

The SZ1018 allow DI1 to be set for fan proving to 

protect equipment on fan failure. To utilize this, a 

pressure or current switch is required, which indicates 

when the fan is running. If the thermostat turns on the 

FAN, and DI1 is not closed after thirty seconds, the 

system will go to OFF, disabling all outputs, the fan 

LED will turn off, and the service LED will be lit until 

the system is manually reset by switching the system 

to a mode other than OFF.  

DI2 SETPOINT SHIFT

The SZ1018 allow DI2 to be set for setpoint shift for 

energy demand setback. This is enabled by setting 

DI2 to the MONITOR mode. A digital contact that 

closes when setback is needed should be wired into 

DI2. You may specify a number of degrees such that, 

when the thermostat is operating in the occupied 

mode, and DI2 is closed, the heating setpoint will 

be lowered this number of degrees, and the cooling 

setpoint will be raised this number of degrees. The 

fan will continue to operate according to its occupied 

setting. If you are using DI2 as monitor for another 

purpose, make sure to set the setpoint and shift value 

to zero.

STAGE OUTPUT PARAMETERS

Heat Setpoint

Cool Setpoint

ON

ON

ON

ON

OFF

OFF

OFF

OFF

Differential

Differential

Offset

Offset

Differential

Differential

The SZ1018 will control up to two stages of either 

heating or cooling.
For each stage, you may specify an offset and a differ-

ential value. The offset value is the amount away from 

the setpoint a stage will turn off. By assigning a stage 

a value other than zero, you “anticipate” that the resid-

ual heat or cooling in the duct or the other stages will 

bring the temperature back to setpoint. In most cases, 

the first stage is set to zero. The differential value is 

the difference between the on and off points. 

ANALOG OUTPUT PARAMETERS

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

 4                         20

P

Z

o

n

e

 

T

e

m

p

Output

   (mA)

P

Output

   (mA)

DIRECT ACTING

REVERSE ACTING

P

P

Output

   (mA)

Output

   (mA)

Z

o

n

e

 

T

e

m

p

P

P

Output

   (mA)

Output

   (mA)

P

P

Z

o

n

e

 

T

e

m

p

CSP

CSP

HSP

HSP

CSP

CSP

HSP

HSP

Summary of Contents for Superzone SZ1018

Page 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Page 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Page 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Page 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Page 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Page 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Page 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Page 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Page 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Page 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Page 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Page 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Page 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Reviews: