background image

Wiring                                    

The SZ1018 use standard terminal designations for wir-

ing. See diagram below.

REMOTE SENSOR WIRING

Use 18 AWG shielded twisted-pair grounded at the sen-

sor mounting location. Sensor wiring runs of up to 250 

feet are attainable if properly shielded wire is used and 

the installation environment is free of electrical noise.  

Sensor wire should be kept at least five feet away from 

line voltage wiring.
The SZ1018 accept two remote sensors.  Consult the 

TS Series Temperature Sensor Submittal Data sheet for 

a complete listing of packaging and application styles. 

When using TCS Basys Controls three-wire sensors, 

use the black and red leads and either clip or twist off 

the white lead. Make sure that the dip switches are set 

for the sensors you are using.

POWERING THE SZ1018

The SZ1018 are powered from 24 VAC +/- 20 %. 

If wiring for communications, dedicated power must be 

used to power the SZ1018. Several S-series thermostats 

may be powered from the same transformer, provided 

that the transformer has sufficient power, although the 

polarity must be kept the same throughout because 

these are half-wave rectified devices. (SZ1018 thermo-

stats require 8 VA @ 24 VAC).

When the SZ1018 are used as a stand-alone thermostat 

without communications, the unit transformer may be 

used to power it. However, using separate power will 

eliminate possible ground loops which may damage the 

thermostat. 

Packaged Unit/Modulating Terminations

3

4

4

4

5

5

Zone/Return 

Air Temp

Discharge 

Air Temp

R

G

Y1

or

W1

Y2

or

W2

Time Clock

Output

+

-

5

Outdoor 

Air Temp

7

6

Damper

2

+

6

HWV 

or 

CWV

A

   

 B

8

8

A

B

1

R

E

F

CAUTION

When multiple TCS devices are

using a single transformer, the 

polarity of the power wiring must 

be maintained because all TCS 

devices are half-wave rectified 

and have common return paths.

!

!

1

2

For communication wiring, 

use twisted, shielded 18 AWG. 

Must be run separately.

Dry momentary contact.

Must not be powered.

24 VAC transformer. See pow-

ering instructions.

3

4

Dry contact. Must not

be powered.

Sensor input wiring 18 AWG,  

twisted, shielded pair.

6

7

4 to 20 mA output. 600 ohm max. Do not power actua-

tor with power from the thermostat. The thermostats 

are half-wave rectified, whereby the power ground is 

common with the signal ground.
Up to nominal 28 VAC from equipment transformer.
Add 500

 resistor (included in bag) to convert 0/4 to 

20mA to, 0/2 to 10 VDC. 

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

2

8

5

Summary of Contents for Superzone SZ1018

Page 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Page 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Page 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Page 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Page 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Page 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Page 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Page 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Page 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Page 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Page 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Page 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Page 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Reviews: