background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

10

turn on for that length of time on powerup. Setting 

each unit to a different delay allows you to soft start 

your system, and thus prevent this peak.

Checkout & Troubleshooting        

CHECKOUT
Note:

 The fan has a minimum on and off time of 30 

seconds. The heating and cooling stages have a mini-

mum on and off time of 2 minutes. 
You may verify the status of heating and cooling stag-

es and fan in monitoring screens 5, 6, and 7, which 

are accessed by pressing the SERVICE STATUS but-

ton. 

V1.0

SZ1018

TCS

MON

12:00 AM              72F

1. Verify all wiring prior to powering the thermostat.

2. Turn power on. The thermostat will display a 

momentary screen with the model number , and 

then the main monitoring screen with the time, day 

and current temperature. 

3. Press the PROGRAM SETUP button until you 

reach the screen # 14 which allows you to set the 

occupant setpoint adjustment limits. Change this to 

+/-20 °F (11.1 °C). Press the PROGRAM SETUP 

button once more to store the change. Then press 

the SERVICE STATUS button once to exit the pro-

gramming. 

4. Press the FAN SWITCH button to access the 

fan mode and change the mode to AUTO. Press 

the FAN SWITCH button once more to store the 

change.  Press the SYSTEM SWITCH button to 

access the system mode and change the mode to 

AUTO. Press the SYSTEM SWITCH button once 

more to store the change.  

5. Verify that the thermostat is operating in the occu-

pied mode by making sure that the top LED is lit. If 

not, press the OVERRIDE button. The LED should 

light up. 

6. Take note of the current temperature reading. 

Press the WARMER (up) button. The setpoint 

adjustment screen should now be showing. Press 

the WARMER button until the heating setpoint is 

greater than the current temperature by at least 

five degrees. The fan will come on. The heating 

stage(s) will sequence on after 30 seconds. 

7. Press the cooler (down) button until the heating 

setpoint is one degree less than the current tem-

perature. The heating stage(s) will sequence off. 

The fan will turn off 30 seconds after the last heat-

ing stage. 

Use programming steps #28 through #32 to program 

the operating parameters for analog output 1. Use pro-

gramming steps #33 through #38 to program the oper-

ating parameters for analog output 2.
Select whether the analog output is set for heating, 

cooling or aquastat. Select direct or reverse action. 

Select whether you want the analog output to modulate 

from 4 to 20mA or 0 to 20mA. Select the unoccupied 

action ("20mA or 0 / 4mA" will hold the analog out-

put device open or closed during unoccupied times. 

"Modulating" will modulate the analog output device to 

maintain the unoccupied heating or cooling setpoint.). 

Enter a proportional band (throttling range) in degrees.

P+I OPTION

The SZ1018 also have a P+I option. Without enabling 

this option, stages turn on and off based on tem-

perature vs. setpoint alone, as described above. By 

enabling this option, you add a time factor to anticipate 

heating and cooling. 

DI2 AQUASTAT

DI2 may be set as an aquastat function. When DI2 is 

selected to have an aquastat function, and the analog 

output is selected to have an aquastat function, opera-

tion is as follows.
With DI2 "Open", the analog output operates in cool-

ing mode, and uses selected direct or reverse action. 

When DI2 is "Closed", the analog output operates in 

heating mode, and uses the opposite of the selected 

direct or reverse action.

SMART RECOVERY

“Smart Recovery” may be enabled. It ramps the set-

point 4°F/hr. when going from the unoccupied  mode to 

the occupied mode. At the beginning of the occupied 

mode, the occupied setpoint will be reached, many 

times without the need for the second stage to come 

on. This feature is automatically disabled when DI3 is 

set to external time clock. 

BUILT-IN DELAYS

The SZ1018 have delays built into the programming 

sequences to protect equipment. The fan has a mini-

mum on and off time of 30 seconds. When the fan is 

in AUTO or COOL mode, it will come on 30 seconds 

before the heating or cooling stages are allowed to 

sequence on, and remain on for 30 seconds after the 

heating or cooling stages sequence off. Each stage 

has a minimum on and off time of two minutes. There 

is a minimum of two minutes between when one stage 

turns on until the next stage is allowed to turn on, as 

well as when one stage turns off until the next stage is 

allowed to turn off.

DELAY ON POWERUP

The SZ1018 have an adjustable delay on powerup. 

When several thermostats are used at one location, 

and the power goes out, most thermostats turn all of 

the units back on at the same time on regain of power, 

creating a peak. The thermostat allows you to set a 

value, in seconds, where no outputs are allowed to 

Summary of Contents for Superzone SZ1018

Page 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Page 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Page 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Page 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Page 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Page 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Page 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Page 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Page 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Page 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Page 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Page 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Page 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Reviews: