background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

8

SETBACK AND OVERRIDE APPLICATIONS

In most applications, it is desired to maintain a regular 

schedule, and allow timed override with the button on 

the face or with a remote momentary contact. 
To allow a regular schedule, and also automatically 

override with the use of occupancy or light sensor, 

set DI3 to override and set it up so that the contact is 

closed when you want the override.  
For applications where a room might not be used on a 

regular schedule, such as conference rooms, set DI3 

to time clock and close the contact when you want the 

room occupied, such as with a switch or wind-up timer. 

If each occupancy period is about the same, (theaters, 

meetings) another option is to set the DI3 to time 

clock, and use the timed override button to put the unit 

in occupied mode. 
To make the unit always occupied, set DI3 to time 

clock and short the DI3 terminal to ground. 

DISCHARGE AIR TEMPERATURE SENSING

The SZ1018 accept a remote 1000 

 discharge air 

sensor (TS1009 or TS1002) for monitoring purposes.  

(See setup instructions for dipswitch placement for this 

option.)
Choose YES in programming screen #39 only if you 

are using a discharge air sensor and you want to 

enable the discharge air temperature high and low 

limit functions or discharge air reset function. See 

Discharge Air Reset section for further programming 

options. If NO is chosen, the discharge air is still moni-

tored.
When the function is enabled, a LOW LIMIT and HIGH 

LIMIT are entered in steps #40 and #41. If the HIGH 

LIMIT is reached, the fan and heating stages will be 

turned off and will remain off until the discharge air 

temperature falls 3° below that limit. If the LOW LIMIT 

is reached, the fan and cooling stages will be turned 

off and will remain off until the discharge air rises 3° 

above that limit. When either limit is reached, the ser-

vice LED will be on until normal operation resumes.
The SZ1018 can use a remote discharge temperature 

sensor for changeover from heating to cooling based 

on the ANALOG SETPOINT set in step #25.
The discharge air span is 0 to 150 °F (-17.8 to 65.6 

°C).

ANALOG OUTPUT / DISCHARGE AIR RESET

The analog output on the SZ1018 are used to control 

the heating or cooling in a space. To use the discharge 

air reset function, a discharge air sensor must be 

installed. In programming step #30, the discharge air 

sensor must be enabled. In programming step #42, 

the control must be based on DISCHARGE air. 

(Do not use with Zoning System)

In programming screen #43, you are asked to enter 

a discharge air setpoint. The discharge air tempera-

ture will be controlled to this setting by modulating the 

heating or cooling device.

Operation                              

UNOCCUPIED SETBACK

The SZ1018 operate in either an occupied or unoc-

cupied mode. During the occupied mode, the occupied 

heating and cooling setpoints will be maintained, and 

the fan will operate according to its occupied setting. 

During the unoccupied mode, the unoccupied heating 

and cooling setpoints will be maintained, and the fan 

will operate according to its unoccupied setting. The 

occupied LED will be lit when the unit is operating in 

the occupied mode.
The occupied schedule may be set utilizing the inter-

nal time clock or DI3 may be used with an external 

time clock, whereas when DI3 is closed, the unit is in 

the occupied mode. The Smart Recovery function is 

disabled when DI3 is used for external time clock.

OVERRIDE

A timed override is available using the button on the 

face of the thermostat or through momentary contacts 

wired into the OVR terminal. The amount of time the 

unit will be overridden is set from 0 to 255 minutes in 

the programming screen. This override behaves differ-

ently depending on the mode the thermostat is operat-

ing in (occupied or unoccupied) and the options that 

have been enabled within the software.
In standard mode, the override only activates in unoc-

cupied mode and takes the thermostat into occupied 

mode. If "Override for Occupied Period" is enabled 

using the software, the override also activates in occu-

pied mode and takes the thermostat into unoccupied 

mode. In either case, you are able to view the time 

remaining in the override period both within the soft-

ware and by using the service button to scroll through 

the status screens. If the occupant desires to return 

the thermostat to unoccupied or occupied operation 

(depending on how the override was used) before the 

override time remaining elapses, they may press the 

override button again.
Additionally, an "Override Hold" feature is built into the 

thermostats. When in unoccupied mode, pressing the 

override once and then pressing/holding it for 5 sec-

onds puts the thermostat into a "hold” mode (the over-

ride LED on the thermostat will flash quickly to confirm 

the mode change). In this mode, the override setpoints 

are used until the next occupied period is reached or 

until the thermostat is manually taken out of the "hold" 

mode by pressing the override button again. This 

feature also works when the "Override for Occupied 

Period" is enabled BUT starting from the occupied 

mode and holding the thermostat in the unoccupied 

state.
A continuous override is available through the DI3 

contact or the software. If DI3 is set to external over-

ride, the unit will be in the occupied mode whenever 

the DI3 contact is closed. When using this option, the 

timed override may still be activated. 

Summary of Contents for Superzone SZ1018

Page 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Page 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Page 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Page 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Page 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Page 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Page 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Page 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Page 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Page 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Page 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Page 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Page 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Reviews: