5. Operation and Configuration
5.1 Double Checking
Make sure the DC input voltage of this system is the same as the nominal voltage of battery.
NEVER try to connect DC input of different voltage to SIES system.
Make sure the PV input voltage of the system is in the recommended range of Solar Mate MPPT
charge controller.
Check the polarity of DC terminals on battery, otherwise the system cannot be switched on.
Make sure the AC inputs and AC outputs are correct to avoid short circuit.
5.2 Switch on the system
It is strongly recommended to switch on the system following the below sequence:
Battery
→
Energier Pro Inverter
→
AC input
→
Solar Mate MPPT charge controller
→
PV input
1) Turn on the input circuit breaker of battery.
2) Switch on the main switch of Energier Pro
to “ON”, all LED will be light on for self-examining.
Afterwards the AC is available at AC output of Energier Pro. The
LED of “Inverter” will be light
on.
3) Next switch on the circuit breaker of AC input, Energier Pro bi-directional inverter will work under
bypass mode to power the loads, and meanwhile start the battery charger (the charger is active
or not depends on the setting status of AC charger). Both the
LED of “Bypass” and “Charger” in
the front panel of Energier Pro should be light on.
4) Press the
”Power On/Off” button in the front panel of Solar Mate will switch on the MPPT
charger controller. In case there are two units of Solar Mate, please switch on the first unit of
Solar Mate and then wait for at least for 10 seconds before switching on the second unit of Solar
Mate.
5) Turn on the power switch of PV input. After one minute, Solar Mate MPPT will start to charge the
connected battery and its LCD screen will display system status.
6) As soon as Cyber starts to display system status, please setup the battery parameters.
Before switching on Energier Pro bi-directional inverter, ensure that the locker device
in Maintenance Bypass switch was secured and Maintenance Bypass switch is on
“OFF” position.