Page 38
B-210 / B-200 Curtis DC System Operator Manual
MB-210-14
Troubleshooting Instructions
If a fault occurs, count the number of flashes between pauses and refer to the table below.
Note: If there is no discernible pause then it is an indication of fault code 1.
Code
CAUSE
SOLUTION
1
High battery voltage
Check battery size and condition.
Fault will clear automatically once the
condition has been corrected.
2
Low battery voltage
Check battery size and condition.
Fault will clear automatically once the
condition has been corrected.
3
Charge time out
caused by battery
pack not reaching
r e q u i r e d v o l t a g e
or charger output
reduced due to high
temperatures.
Check battery connections.
Confirm that the battery type matches
selected charge profile
Operate the charger at a lower ambient
temperature.
Reset the charger by interrupting AC
power for 15+ seconds.
4
Battery could not be
trickle charged up
to minimum voltage.
Check for shorted or damaged cells.
Reset the charger by interrupting power
for 15+ seconds.
5
Charger shutdown
due to high internal
temperature.
Ensure sufficient cooling airflow.
Reset the charger by interrupting AC
power for 15+ seconds.
6
Internal charger fault
Reset the charger by interrupting
AC power for 15+ seconds. Refer to
qualified technician if fault persists.
1) Ammeter
•
Solid
: Displays scale of output during bulk phase.
•
Flashing
: Output has been reduced due to high internal
charger temperature.
•
No battery connected
: Displays charge profiles 1-6.
2) Bulk Charge Indicator
•
Solid
: Bulk charge phase completed (80% charged) and is
in absorption phase.
•
Flashing
: Displays charge profile number if no battery is
connected.
3) Charge Completion Indicator
•
Solid
: Charging complete and maintenance mode is active.
•
Flashing
: Absorption phase completed and is in finishing
phase.
4) AC Indicator
•
Solid
: AC power is present.
•
Flashing
: Low AC voltage. Refer to qualified technician.
5) Fault Indicator
•
Charger fault. Refer to troubleshooting information below.