90
Operation description
Required tool
Approximate timing
Operation check
Turn on the CM auxiliary power supply then check
the following:
-
The “Power“ LED must light up immediately;
-
The “Ready“ LED must light up continuously
within 15 s after switching on;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must close within
15 s.;
-
The “Malfunction or Loss of auxiliary
suppl
y“ relay contact must change its state
1)
;
-
The “ISM main contact position” relay contact
must not change its state;
-
ISM main contacts must not change their
state (ISM shall remain open).
Visual check, no tool is required
1 minute
Apply close command to the CM then check the
following:
-
The “Power“ LED must light continuously;
-
The “Ready“ LED must light continuously;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must not change
its state;
-
The “Malfunction or Loss of auxiliary
supply“ relay contact must not change its
state;
-
The “ISM main contact position” relay contact
must change its state;
-
ISM main contacts must change their state
(ISM shall be closed).
Visual check, no tool is required
1 minute
Apply trip command to the CM then check the
following:
-
The “Power“ LED must light continuously;
-
The “Ready“ LED must light continuously;
-
The “Malfunction“ LED must not light up;
-
The “Ready“ relay contact must not change
its state;
-
The “Malfunction of Loss of auxiliary
supply“ relay contact must not change its
state;
-
The “ISM main contact position” relay
contact must change its state;
-
ISM main contacts must change their state
(ISM shall be open).
Visual check, no tool is required
1 minute
1) „As earlier, after CM power supply disconnection this relay indicated the CM state: “Power supply voltage is absent for more than 1.5 seconds“
Summary of Contents for VCB Series
Page 1: ...COMPATIBLE SERIES USER GUIDE...
Page 2: ......
Page 4: ......
Page 5: ...1 Product description...
Page 13: ...13 2 Nameplates and seals...
Page 18: ...18 3 Product handling...
Page 37: ...4 Installation...
Page 87: ......
Page 88: ...5 Commissioning...
Page 94: ...94 Figure 155 The connection points of the contact resistance meter...
Page 95: ......
Page 96: ...6 Operation...
Page 100: ...7 Maintenance and troubleshooting...
Page 105: ......
Page 106: ...8 Disposal...
Page 109: ...109 Appendix 2 Overall Drawings...
Page 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Page 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Page 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Page 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Page 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Page 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Page 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Page 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Page 129: ...Appendix 3 Secondary Schemes...
Page 130: ...130...
Page 131: ...131...
Page 132: ...132...
Page 133: ...133...
Page 134: ...134...
Page 135: ...135...
Page 136: ...136...
Page 137: ...137...
Page 138: ...138...
Page 139: ...139...
Page 140: ...140...
Page 142: ...Bartlett...