103
7.2 Secondary circuits
The CM is inherently maintenance free. However when maintenance is carried out on the switchgear then
commissioning tests should be repeated. It is also recommended to conduct regular visual checks of the
module housing and insulation of the wires connected to the CM. Test results should be treated as given in
the Table 19.
Table 19 - List of tests and check-ups of CM during maintenance
Operation description
Required tool
Approximate timing
Auxiliary circuits insulation check
Connect all points of the secondary circuits
with a shorting wire. ISM coil connection
wires must be disconnected from connector
X3 of the CM before the test.
Wires
5 minutes
Connect the shorting wire to the high
potential lead of the high voltage tester and
ground the circuit breaker housing. Start
with zero volts, gradually increase the test
voltage to 1500 V RMS, 50 or 60 Hz.
Maintain test voltage for one minute.
Power frequency withstand voltage test set
3 minutes
If no disruptive discharge occurs, the
secondary circuits insulation level is
satisfactory.
Power frequency withstand voltage test set
-
Disconnect the shorting wire and reattach
the wires to connector X3 of the CM.
Visual check, no tool is required
5 minutes
Summary of Contents for VCB Series
Page 1: ...COMPATIBLE SERIES USER GUIDE...
Page 2: ......
Page 4: ......
Page 5: ...1 Product description...
Page 13: ...13 2 Nameplates and seals...
Page 18: ...18 3 Product handling...
Page 37: ...4 Installation...
Page 87: ......
Page 88: ...5 Commissioning...
Page 94: ...94 Figure 155 The connection points of the contact resistance meter...
Page 95: ......
Page 96: ...6 Operation...
Page 100: ...7 Maintenance and troubleshooting...
Page 105: ......
Page 106: ...8 Disposal...
Page 109: ...109 Appendix 2 Overall Drawings...
Page 112: ...112 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 113: ...113 ISM15_LD_8 PCD 210 mm Weight 26 kg...
Page 114: ...114 ISM15_MD_1 150_L PCD 150 mm Weight 33 kg ISM15_MD_1 210_L PCD 210 mm Weight 35 kg...
Page 115: ...115 ISM15_MD_3 Weight 13 kg ISM15_Shell_2 150_L PCD 150 mm Weight 51 kg...
Page 120: ...120 ISM15_HD_1 275 PCD 275 mm Weight 72 kg ISM25_LD_1 210_Par2 PCD 210 mm Weight 36 kg...
Page 123: ...123 ISM25_LD_2 2 PCD 150 mm Weight 37 kg ISM25_LD_3 Weight 14 kg...
Page 125: ...125 Dimensions of Control Module CM_16_1 Par1_Par2_Par3_Par4_Par5 Weight 1 kg...
Page 127: ...127 Dimensions of Interlocking Kits CBkit_Interlock_1 CBkit_Interlock_3...
Page 128: ...128 CBkit_Interlock_4 CBkit_Interlock_5...
Page 129: ...Appendix 3 Secondary Schemes...
Page 130: ...130...
Page 131: ...131...
Page 132: ...132...
Page 133: ...133...
Page 134: ...134...
Page 135: ...135...
Page 136: ...136...
Page 137: ...137...
Page 138: ...138...
Page 139: ...139...
Page 140: ...140...
Page 142: ...Bartlett...