13
-
use only M-030000CC50 cable or equivalent.
- In case of long sections of cables (> 20 m) for N.O./N.C. controls (e.g. OPEN / CLOSE, STOP, PEDE-
STRIAN, etc.), in order to avoid gate malfunctions, it will be necessary to uncouple the various
controls using RELAYS or using our 750T-RELE device.
2. TESTING
When you have completed the connection:
• All the green LEDs must be on (each of them corresponds to a Normally Closed input). The go off
only when the controls to which they are associated are operated.
• The red DL5 LED must be off (corresponding to the Normally Open OPEN/CLOSE input). It only
comes on when it is activated by the control to which it is associated.
3. TECHNICAL CHARACTERISTICS
Board power supply
13,5V AC - 50 Hz
Max motor 1 power DC
50 W - 18V DC
Max motor 2 power DC
50 W - 18V DC
Fast acting fuse for protection of input power supply 13.5V AC (F1 - 5x20)
F 16 A
Fast acting fuse for motors protection (F2 - 5x20)
F 10 A
Fast acting fuse for protection of auxiliary circuits 18V DC (F3 - 5x20)
F 3,15 A
Motor power supply circuits voltage
18V DC
Auxiliary device circuits supply voltage
18V DC
Logic circuits supply voltages
5V DC
Operating temperature
-20 °C ÷ +55 °C
4. TERMINAL BOARD CONNECTIONS
Terminals
Function
Description
1 - 2
POWER SUPPLY
FS1 - FS2:
board supply input 13.5 Vac – Powered by the toroidal
transformer housed in the SPIN12Q motor and protected by a
fuse (F 6,3A) on the 230 Vac power supply;
3 - 4
18V DC
MOTOR 1
motor 1 (M1) supply output 18 Vdc max. 50 W;
5 - 6
18V DC
MOTOR 2
motor 2 (M2) supply output 18 Vdc max. 50 W;
7 - 8
AERIAL
433,92 MHz built-in RX aerial input; 7 = Signal 8 = Earth;
9 - 11
OPEN/CLOSE
Input for open/close push button (normally-open contact): for us-
age, see the functions of dip switches 2-4; 9 = Open/close; 11 =
Common;
10 - 11
STOP
Stop push button NC (normally closed) contact. After a stoppage,
the system always starts again only after receiving a command
from the On button or radio transmitter. 10 = Stop; 11 = Com-
mon;
11 - 12
SENSITIVE
EDGE
Resistive sensitive edge input (DIP 5=ON); sensitive edge input –
fixed edge (DIP 5=OFF); 11 = Common; 12 = Sensitive edge.
If neither the resistive sensitive edge nor the fixed edge are used,
set DIP 5 to OFF and short circuit terminals 11 and 12;
13 - 14
COURTESY
LIGHT
Output for auxiliary courtesy light 18 Vcc max 15 W;
(
13 = POSI-
TIVE - 14 = NEGATIVE
)
;
15 - 16
FLASHING LIGHT
18 Vdc max. 20W output for flashing light supply (15 = POSITIVE -
16 = NEGATIVE), flashing signal supplied by the control unit, rapid
for closing, slow for opening;
ENGLISH