1. ELECTRIC ARRANGEMENTS
NOTE:
The grey part indicates
the survey zone of radar
and sensors.
The number of cables
and the relevant section
in mm is indicated for
every device.
1
3
4
8
9
6
5
2
7
1) EXTERNAL RADAR (4x0,5mm)
2) INTERNAL RADAR (4x0,5mm)
3) OPENING CONTROL (2x0,5mm)
4) PROGRAM SELECTOR (4x0,5mm)
5) SAFETY SENSOR FOR CLOSING (6x0,5mm)
6) SAFETY SENSOR FOR OPENING(6x0,5mm)
7) BRINK OPERATOR (mains power supply 3x1,5mm)
8) ELECTRIC LOCK (2x1mm)
9) FLOOR STOP
• The power supply line must be protected against short circuit and dispersion to
ground.
• On the power supply mains, provide for an omni-polar switch/selector with
contact opening distance of at least of 3 mm.
• Use self-extinguishing cables for electric connections.
• Separate the mains power supply line from the very-low voltage line relative to
control and safety accessories.
• On the plastic side panels of the Brink operator there are the holes that must be
broken open, through which the electric cables must be inserted. The installer
must made the power supply cable stable inside the operator and, particularly,
limit the peeling of cable primary sheath so that the air and surface distances
are not reduced if a connector detaches from the terminal.
• If operator is installed on a door leaf, perform electric connection by a bran
-
ching box with suitable flexible unions and pipes, available on the market.