tau DC18 Installation Manual Download Page 12

12

it will propose the SETUP procedure automatically. To start the procedure, press the P1 key.

To start the SETUP of the stroke, press the P1 key, the DL1 LED will start to flash yellow and, 

subsequently, the door will start a slow opening and closing maneuver to find the opening 

and closing limit switches. At the end, the door will perform a complete opening and closing 

maneuver at standard speed. Once the setup is done, the door must be closed and the DL1 

LED must flash green.

The automation will therefore work with the standard factory settings. In case an interven

-

tion is required to change the operating parameters, the digital keyboard must be used by 

accessing the various menus

 SENSOR TEST SETTING 

•    Use only sensors which feature testing wires, connecting these to the wire terminals 8 

and 10 of the controller DC18;

•   Set DIP #15 and #16 on to ON in order to enable the test;
•     Test will be performed at the beginning of each cycle (except when reversing motion)

.

BATTERY CHARGER KEY

Key:

     

LED steady on;        

 

LED flashing;

GREEN LED – battery charger 

status

     off

battery charger off;

  flashing every 2 seconds

initial slow charge;

  continuous flashing

under fast charge;

  flashing every 4 seconds

in backup;

  steadily lit

battery charged;

RED LED – fault diagnostics

     off

everything OK;

  steadily lit

FAULTY battery (cell voltage < than the minimum 

or …..)

  continuous flashing

short circuit

  flashing every 2 seconds

battery not connected

 AUTOMATIC OPERATION RESETTING - REALIGNMENT

When the board is powered or if the status of the inputs is unknown, the software must 

realign the automation to determine the initial position. 

The direction of the realignment depends on the program selected and the command given.

ATTENTION: if there are any “motor” alarms, the automatic reset timer is inhibited.

ENGLISH

Summary of Contents for DC18

Page 1: ...INSTALLATION GUIDE GUIDA ALL INSTALLAZIONE NOTICE D INSTALLATION IT Istruzioni originali DC18 DC18 M 1 2 3 4 DC18 P D MNL0DC18 08 05 2023 Rev 08...

Page 2: ...COMMON green and blue COMMON TEST SENSOR brown NOT USED GND black EMERGENCY EMERGENCY START 20 18 START 20 19 1 2 3 4 5 6 7 DOORSS340 1023T 1 2 3 4 5 6 7 DOORSS340 1023T 1 2 3 4 1 2 3 4 TEST SENSOR gr...

Page 3: ...SE NEUTRO SCHEDA CARICA BATTERIE BATTERIA SERR ELET MOTORE SECONDARIO TF PRIMARIO TF F1 3 15 A F2 6 3 A F3 2 A LED4 LED5 TERRA 230V ac SEZIONATORE ALIMENTAZIONE DI RETE MOTOR MOTOR ELECTROLOCK BATTERY...

Page 4: ...USED GND EMERGENCY EMERGENCY START 20 18 START 20 19 1 2 3 4 5 6 7 DOORSS340 1023T 1 2 3 4 5 6 7 DOORSS340 1023T TEST SENSOR 24Vcc RADAR OUT N A SECURITY OP N C SECURITY CL N C RADAR IN N A SENSOR OP...

Page 5: ...RIMARIO TF F1 3 15 A F2 6 3 A F3 2 A LED4 LED5 TERRA 230V ac SEZIONATORE ALIMENTAZIONE DI RETE MOTOR MOTOR ELECTROLOCK BATTERY BATTERY OUTSIDE SENSOR S 10DOORRAD2 TEST POWER Mors 10 Brown Mors 8 Grey...

Page 6: ...ied personnel in compliance with cur rent laws regulations and directives When designing its products TAU observes all applicable standards please see the attached decla ration of conformity but it is...

Page 7: ...mni polar switch selector with contact opening distance of at least of 3 mm Use self extinguishing cables for electric connections Separate the mains power supply line from the very low voltage line r...

Page 8: ...use for protection of auxiliary circuits 24 V CC F1 5x20 2 A Fast acting fuse for motor protection 40Vcc F2 5x20 6 3 A Motor power supply circuits voltage 40 V DC Auxiliary device circuits supply volt...

Page 9: ...V 50hz Terminals Input Output Description 1 PHASE 230V AC 2 GROUND 3 NEUTRAL 230V AC On request 115 Vac 10 60Hz CONNETTORE J2 transformer primary connector CONNETTORE J3 transformer secondary connecto...

Page 10: ...V DC 17 GND CONNETTORE J7 battery connector CONNETTORE J8 battery charger board connector CONNETTORE J9 connector for T WIFI CONNETTORE J11 connector for lid button CONNETTORE J12 connection for T LIN...

Page 11: ...efore proceeding with the SETUP of the stroke use the dipswitch to select the type of au tomatic swing door and its characteristics 1 AUTOMATION TYPE ON T SIDE S gearmotor with closing spring OFF T SI...

Page 12: ...minals 8 and 10 of the controller DC18 Set DIP 15 and 16 on to ON in order to enable the test Test will be performed at the beginning of each cycle except when reversing motion BATTERY CHARGER KEY Key...

Page 13: ...ation in progress program change Allarmi automazione red 1 error photocell test failed red 2 error obstacle present red 3 error no voltage red 4 error automation in unknown status red 5 error automati...

Page 14: ...door found an ob stacle Remove the obstacle The following cycle is per formed at reduced speed The door has excessive friction which is seen as an obstacle Check the door movement if necessary adjust...

Page 15: ...that the command actuators for door opening the program selector and the electric lock must be connected to the Master operator The safety sensors installed on the master leaf must be connected to th...

Page 16: ...DC18 M SLAVE 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 J4 J10 J12 J13 J14 A B DC18 M MASTER 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 J4 J10 J12 J13 J14 A B B A ENGLIS...

Page 17: ...17 ENGLISH...

Page 18: ...18...

Page 19: ...19...

Page 20: ...0376 info tauitalia com www tauitalia com Foglietto illustrativo CARTA Raccolta differenziata Segui le indicazioni del tuo comune N B togliere i punti metallici Instruction leaflet PAPER Waste separat...

Reviews: