background image

LEAKAGE LOCATION DETECTOR

Buzzer Stop

Reset

Leak Point

AD-AS-1LDMA

 

Communication speed terminal setting switch

S

RS485

S

RS485

For maintenance use

(Do not use them.)

Modbus address setting switch

(No. 1 to 15)

Power indicator LED

Alarm indicator LED

Maintenance indicator LED

Buzzer stop switch

Alarm cancel switch

LCD
The items to be displayed are as follows:
Modbus address
Sensor length
Water leakage point
Details of the error

Operational setting switch

Connection terminal board (M3)

Sensitivity fine adjustment VR
* This has already been adjusted before shipment.
Do not change the setting.

* Contact operation
Contact a can be changed to Contact b
by adjusting the setting of the operational
setting switch.
(Refer to Attached Drawing 3.)

4-20 mA
output

Sensor

connection

AD-LS

Alarm

contact

(* Contact 1a)

B

ra

id

e

d

 w

ir

e

In

s

u

la

te

d

 w

ir

e

R

e

s

is

ta

n

c

e

 w

ir

e

C
O

M

N
O

Power source

* AC24V or DC24V

G

ro

u

n

d

in

g

 

c

o

n

n

e

c

ti

o

n

E

H

G

F

E

D

C

B

A

8

7

6

5

4

3

2

1

H

G

F

E

D

C

B

A

8

7

6

5

4

3

2

1

Attached Drawing 2

* For Modbus communication use

* Power source
An AC 24 V input has no polarity.
The + and - symbols apply to a DC 24 V input.
Two terminals to which connections are made are
available at each location. Making connections at
one of the locations will activate the system.
Use the other for connection wiring.

*Modbus RS485
Two terminals to which connections are made are
available at each location. Making connections at
one of the locations will activate the system.
Use the other for connection wiring.

mm

-/-

Approved by

N

am

e

Prepared by

Checked by

Scale

Unit

Prepared on

TATSUTA Electric Wire & Cable Co., Ltd.

Revision date

Prepared by

Checked by

Approved by

Reason for revision

Water Leakage

 Location Detector

(AD-AS-1 LDMA)

Explanation of

Individual Parts

Length

2014.12.01

 

In

su
la

te

d

 

wi
re

 

B

ra

d

e

d

 

wi
re

 

Resista

n

c

e

 

wi
re

 

Summary of Contents for AD-AS-1LDMA

Page 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Page 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Page 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Page 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Page 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Page 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Page 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Page 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Page 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Page 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Page 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Page 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Page 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Page 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Page 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Page 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Page 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Page 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Page 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Page 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...

Reviews: