4.  Configuration  of  Water  Leakage  Location  Detecting  System 

The Water Leakage Location Detection System consists of the following components: 

1)  Water Leakage Location Detector (AD-AS-1LDMA) 

2)  Water Leakage Sensor (AD-LS) 

3)  Break Detection Terminal (ZT-L2) 

Each  connection  of  terminal  block  is  described  in  Chapter  5.

   

General instrumentation cables:

Joint box

・Central monitoring board
・Sequencer
・Control circuit, etc.

Break Detection Terminal

ZT-L2

Water Leakage 
AD-LS Sensor

Contact output

*Option  

Water leakage location 

data output (4-20 mA 

output)

*電源入力

AC24V

or

DC24V

Water Leakage Location Detector

AD-AS-1LDM

Grounding

Triplex, twisted wiring conductor: 0.9mm

min. in area and 1000m max.

 

in length

Triplex, single wiring conductor: 

φ

10mm min. and 1000m max. in length

LP      1000m
SL      1500m

LEAKAGE LOCATION DETECTOR

Buzzer Stop

Reset

Length

Leak Point

AD-AS-1LDM

Power

E

1

2

3

Sensor

Alarm

COM

NO

Power

Option

AC/DC

AC/DC

Address

RS485

RS485

Setting

S

S

Baud rate

Setting

Maintenance
(Don’t care)

4-20mA

Reports to the host system by Modbus communication.

 

Drawing  2  Water  Leakage  Location  Detecting  System 
 

5.  External  Connection

 

AD-AS-1LDMA has a terminal block as shown in Drawing 3. (Make connections securely in conformance to 
Sections 1 to 5.)

 

 

LEAKAGE LOCATION DETECTOR

Buzzer Stop

Reset

AD-AS-1LDM

① ② ③ ④ ⑤

Power Power Grounding

 

Drawing 3 Layout Drawing of Terminal Block

 

 

5-1  Power  Connection 

Before connection, check that the power supply voltage is within the range of use and check the polarity, then 
connect it securely to the terminal block. 

*  Inputting a power supply voltage outside the range of use may cause malfunctions and failure of the 

detector, so care should be taken.   

 

AC  24V  (DC  24V  +)   

  AC  24V  (DC  24V  -)

 

 

  AC  24V  (DC  24V  +)

 

 

  AC  24V  (DC  24V  -)

 

 

*

 

  and 

  is  terminal  block  for  transition  wiring.  Inside  the  detector, 

  is  connected  to 

,  and 

  is  connected

  to 

Connecting  the  power  source  to 

,

 

  or 

,

 

  may  cause  short,  so  care  should  be  taken.

   

-2- 

 

Power 

AD-AS-1LDMA 

1.0 

AD-AS-1LDMA 

Summary of Contents for AD-AS-1LDMA

Page 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Page 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Page 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Page 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Page 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Page 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Page 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Page 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Page 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Page 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Page 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Page 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Page 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Page 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Page 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Page 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Page 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Page 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Page 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Page 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...