7-2  Operation  Chart  When  Alarm  Hold  Setting  is  Activated 

Changing operational setting switches activates the alarm hold setting for indication and control output contacts. 
For the Operation Chart, refer to Drawing 14. 

 

It  is  possible  to  set  the  control  output  contact  from  the  host  system  by  the  Modbus  communication. 

 

OFF

ON

Lighting 

out

Lighting 

up

OFF

Lighting 

out

OFF

OFF

ON

OFF

Flashing

ON

OFF

ON

ON

OFF

OFF

Open

Open

Closed

Open

Closed

Open

Lighting up

OFF

ON

ON

OFF

OFF

Alarm cancel switch

OFF

ON

ON

OFF

OFF

No 

indication

No 

indication

*1 Indication

Indicating ---

*1 Indication

*2 Indication

*1 The sensor length and the water leakage location are indicated alternately. (Refer to Attached Drawing 4)
*2 For the break indication, the alarm status is not held.

4

mA

4

mA

4

mA

20

mA

OFF

Lighting 

out

No 

indication

Lighting 

out

Power

Power Indicator LED

Water leakage 

detection function

Alarm Indicator LED

Break detection function

Buzzer Stop Switch

Buzzer sounding

Control output contact 

(water leakage: COM-NO)

Control output contact 

(break: COM-NO)

Sensor length indication

Water leakage 

location indication

Water leakage location 

data output 

(4-20 mA output)

6 + 0.03 x water leakage location indication (m) mA

4 + 16 x water leakage location indication (m) / 250 (m) mA

or

 

Drawing 14 Operation Chart-2 

 

Regarding the operation when the alarm hold setting is activated 

When the alarm hold setting is activated, the alarm status is held until the cancel switch is pressed. 

Electric power failure or power-off returns the contact operation status to that when the power source is shut off. 

 

Regarding the Alarm Indicator LED 

The Alarm Indicator LED does not maintain alarm status. The Alarm Indicator LED goes out when the system 
detects recovery from water leakage status and break status. 

If the Alarm Indicator LED continues to flash even after the water leakage sensor is wiped with rags etc., this 
indicates that water leakage may occur at multiple locations. 

After completely drying the water leakage sensor at the location that the indicator displays, press the alarm 
cancel switch. 

*  If drying is insufficient, deviation may occur between the location displayed by the indicator after the alarm 

cancel switch is pressed and the actual water leakage location. 

 

-8- 

Summary of Contents for AD-AS-1LDMA

Page 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LDMA Operation Manual System Equipment Division Electronic Material System Equipment Group Tatsuta Electric Wire Cable Co Ltd...

Page 2: ...Locations easily accessible to the general public Locations close to sources of vibration organic gas or strong electromagnetic induction Locations subject to excessive waste and dust Locations where...

Page 3: ...ks 3 17 Osadano cho Fukuchiyama City Kyoto 620 0853 Tel 81 773 45 6500 Fax 81 773 45 6501 Tatsuta Technical Center 6 5 1 Kunimidai Kizugawa City Kyoto 619 0216 Tel 81 774 66 5550 Fax 81 774 66 5556 Sh...

Page 4: ...ection Function 7 Operation Chart 7 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Modbus Address 9 9 Detection Sensitivity Setting 9 10 Buzzer S...

Page 5: ...stallation The Water Leakage Location Detector AD AS 1LDMA shall be securely installed in a strong housing on the wall etc inside a building Be sure to follow the following instructions when installin...

Page 6: ...sor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA Reports to the host system by Modbus communication Drawing 2 Water Leakage Loc...

Page 7: ...ring make sure that the power is switched off Drawing 4 AD LS Sensor Structure Table 1 AD LS Sensor Configuration Element Configuration Braided wire 0 33mm2 tinned soft copper wire covered with red pl...

Page 8: ...a Output Connection 5 5 1 Connection The AD AS 1LDMA has a function that outputs the water leakage location by DC electrical current Option Use an analog input device with an input resistance of 500 o...

Page 9: ...l analog input devices are broken 2 The input resistance for the external analog input devices is more than 500 If there is no problem with the items above the detector may be out of order Contact the...

Page 10: ...unction 1 Drop tap water on the sensor 2 The buzzer sounds the Alarm Indicator LED lights up and the contacts for water leakage detection function 3 LCD indicates as shown in Drawing 12 Example In the...

Page 11: ...indication No indication 1 Indication Indicating 1 Indication 1 The sensor length and the water leakage location is indicated alternately Lighting out Lighting out 20 Water leakage location data outp...

Page 12: ...er leakage location indication Water leakage location data output 4 20 mA output 6 0 03 x water leakage location indication m mA 4 16 x water leakage location indication m 250 m mA or Drawing 14 Opera...

Page 13: ...o detect fluid with high electrical resistance such as pure water in an environment where the temperature and humidity are stable such as a clean room it is recommended to set the sensitivity level hi...

Page 14: ...larm buzzer Average sound pressure 90 dB 10 cm catalogue value by manufacturer Control output contact Contact Configuration Contacts For specifications refer to Section 11 2 Water leakage 1 for 1a Bre...

Page 15: ...ak Point AD AS 1LDMA Power E 1 2 3 Sensor Alarm COM NO Power Option AC DC AC DC Address RS485 RS485 Setting S S Baud rate Setting Maintenance Don t care 4 20mA mm Approved by N a m e Prepared by Check...

Page 16: ...I n s u l a t e d w i r e R e s i s t a n c e w i r e C O M N O Power source AC24V or DC24V G r o u n d i n g c o n n e c t i o n E H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Atta...

Page 17: ...N Available OFF Contact a ON Contact b Operational setting OFF OFF OFF OFF OFF Activated ON Not activated Alarm hold for water leakage location indication 1 2 3 4 Terminal resistance setting Setting o...

Page 18: ...et Length Leak Point AD AS 1LDMA Modbus address LIT Indication in the case of water leakage detection No 001 SL 400m LEAKAGE LOCATION DETECTOR Buzzer Stop Reset Length Leak Point AD AS 1LDMA Modbus ad...

Page 19: ...ws Addresses 1 to 9 Dials 1 to 9 Address 10 Dial A Address 11 Dial B Address 12 Dial C Address 13 Dial D Address 14 Dial E Address 15 Dial F To set an address between 16 and 127 set the dial at 0 and...

Page 20: ...sing the Reset switch allow the desired number to appear Each time you push the switch the figure increases one by one in order 0 1 2 3 4 5 6 7 8 9 0 When the address you desire is indicated press and...

Reviews: