No.001
SL 400m
LEAKAGE LOCATION DETECTOR
Buzzer Stop
Reset
Length
Leak Point
AD-AS-1LDMA
Method of setting a Modbus Address
①
To set a Modbus Address, operate the rotary switch of the detector.
The addresses that can be set are from 1 to 15.
The address corresponding to a dial is as follows:
Addresses "1" to “9”: Dials “1” to “9”
Address “10”: Dial “A”
Address “11”: Dial “B”
Address “12”: Dial “C”
Address “13”: Dial “D”
Address “14”: Dial “E”
Address “15”: Dial “F”
To set an address between 16 and 127, set the dial at “0 and then use
the buzzer stop switch and the res”et switch. For more information,
refer to the next page.
Note that assigning identical addresses to the same communication line
causes a communication disturbance.