Installation Guide: PowerAire® Quad
r2.0-7/8/14
Quad- S: 16943, 17351 Quad- M: 16886, 16633 Quad- C: 17347, 17348
7510 Montevideo Road
© 2012 Tate Access Floors, Inc.
Jessup, MD 20794
Tel (410)799-4200
11 of 15
11.
Once the value has been set, and all programming completed. Reinstall the DirectAire® or other panel above
the PowerAire® unit and proceed to the next unit. It is best to work right to left due to the connector layout
on the PowerAire® unit. Each subsequent unit can fully access connector points on its neighboring unit,
allowing for easier access to power connections.
12.
The PowerAire® will now run automatically, increasing and decreasing fan speed as the temperature values
change based on changing IT equipment conditions. The unit is meant to function as a hot spot reduction
device, pulling air into areas with little or no static pressure due to underfloor restrictions, and insufficient
floor heights. Best practices dictate that underfloor plenum spaces should have all unnecessary restrictions
removed from beneath the floor, but often site conditions make this difficult or not cost effective.
Figure 18 - Programming Set point for Control
For Quad-Fan M and C units, Skip step 13.