Installation Guide: PowerAire® Quad
r2.0-7/8/14
Quad- S: 16943, 17351 Quad- M: 16886, 16633 Quad- C: 17347, 17348
7510 Montevideo Road
© 2012 Tate Access Floors, Inc.
Jessup, MD 20794
Tel (410)799-4200
6 of 15
Figure 7 - PowerAire
®
Quad Unit Installed on hangers in correct orientation
Figures 8,9 - Installation of PowerAire
®
Quad Unit onto Tool Less Hangers
For Quad-Fan C units, Skip steps 6 and 7.
6.
Plug in the temperature sensor tree into the labeled connection port on the left side of the unit when facing
the rack. Route the temperature probes into the rack. This can typically be done by routing the probes
through the cable entry hole serving the rack, or by drilling a new 0.5” hole at the front of the rack, through
the panel directly below the rack. If a new hole is required, ensure that the hole is sealed after the
temperature probes are completely routed, and that the holes edges are appropriately grommeted to
decrease the risk of cable damage.