background image

©Copyright Task Force Tips LLC 2010-2021

6

LIY-250 May 10, 2021 Rev03

5.0 OPERATING INSTRUCTIONS

5.1 QUICK CONNECT MONITORS

TO INSTALL MONITOR ON INLET ADAPTER:

1. Hold locking pin out. Push coupling up as far as it will go, then release locking pin. This will hold the coupling out of the way while

mounting the monitor onto inlet base.

2. Align the narrow tongue on the monitor inlet with straight ahead reference mark on the inlet adapter, then slide into inlet adapter.

3. Hold locking pin out. Rotate coupling clockwise until threads engage on inlet adapter, then release locking pin. 

4. Continue to rotate coupling until tight. Locking pin will ratchet across detents, but it is not necessary to over-tighten coupling if

locking pin ends up between detent positions. To prevent damage, do not use locking pin as a lever to tighten or loosen coupling.

TO REMOVE MONITOR FROM INLET ADAPTER:

1. Hold locking pin out. Rotate coupling counter-clockwise at least a half-turn to clear the detents, then release locking pin.

2. Continue to rotate coupling until threads are no longer engaged.

3. Lift the monitor out of the inlet adapter.

Figure 5.1

5.2 QUICK CONNECT ELBOWS

Elbow is intended for temporary installation only, so a locking pin is not needed. 

(see Figure 5.1)

The full time swivel joint and tongues engaged into slots are able to prevent accidental disassembly due to forces acting on the hose

line. If desired, a 1/4”NPT pressure gage may be installed in the elbow by drilling thru the blind port shown in section 4.2 using a ¼” drill

bit.

TO INSTALL ELBOW ON INLET ADAPTER:

1. Align narrow tongue on the inlet elbow with straight ahead reference mark in the inlet adapter, then slide into inlet adapter.

2. Rotate coupling clockwise until tight.

TO REMOVE ELBOW FROM INLET ADAPTER:

1. Rotate coupling counter-clockwise until threads are no longer engaged.

2. Lift the elbow out of the inlet adapter.

LOCKING PIN

STRAIGHT AHEAD

REFERENCE MARK

NARROW TONGUE

NARROW SLOT

WIDE TONGUE

INLET ADAPTER
(4" ANSI 150 SHOWN)

WIDE SLOT

NARROW TONGUE

WIDE TONGUE

STRAIGHT AHEAD

REFERENCE MARK

NARROW SLOT

INLET ADAPTER
(4" ANSI 150 SHOWN)

WIDE SLOT

Summary of Contents for LIY-250

Page 1: ...use Operation of this device without understanding the manual and receiving proper training is a misuse of this equipment Obtain safety information at tft com serial number This equipment is intended for use by trained and qualified emergency services personnel for firefighting All personnel using this equipment shall have completed a course of education approved by the Authority Having Jurisdicti...

Page 2: ...d to familiarize firefighters and maintenance personnel with the operation servicing and safety procedures associated with this product This manual should be kept available to all operating and maintenance personnel Hurricane Dual Handwheel Hurricane Hurricane Extended Hurricane Tiller For 4 5 Quick Connect and Valve Under Monitor See Section 3 3 for Flow Pressure Operating Envelope Copyright Task...

Page 3: ...elated to physical injury DANGER An inadequate supply of pressure and or flow will cause an ineffective stream and can result in injury or death Choose operating conditions to deliver adequate fire suppression See flow graphs WARNING This equipment is intended for use by trained personnel for firefighting Use of this equipment for other purposes may involve hazards not addressed by this manual See...

Page 4: ...using injury and property damage if not properly supported Monitors should be securely installed by qualified individuals Mounting objects must be capable of withstanding maximum nozzle reaction force listed in SPECIFICATIONS The monitor must be securely mounted to rigid support members Do not use flanges or pipe made from plastic for monitor mounting Torque all fasteners to specified values WARNI...

Page 5: ...ad trunnion between ports C2 and C3 serves as the Straight Ahead Reference Mark Travel ranges relative to the Straight Ahead Reference Mark can be modified by using Stop Bolts which are used to limit the travel See instruction manual for monitor for use of Stop Bolts Figure 4 2 TO USE 1 4 NPT PORT DRILL THRU USING 1 4 BIT MONITOR WITH 4 5 QUICK CONNECT TYPHOON SHOWN STRAIGHT AHEAD REFERENCE MARK E...

Page 6: ... turn to clear the detents then release locking pin 2 Continue to rotate coupling until threads are no longer engaged 3 Lift the monitor out of the inlet adapter Figure 5 1 5 2 QUICK CONNECT ELBOWS Elbow is intended for temporary installation only so a locking pin is not needed see Figure 5 1 The full time swivel joint and tongues engaged into slots are able to prevent accidental disassembly due t...

Page 7: ...e of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended beneficiary of the equipment shall not be entitled to recover from TFT any consequen...

Page 8: ...g any part of this test must be removed from service repaired and retested upon completion of the repair 7 2 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced equipment is repaired by experienced technicians wet tested to original specifications and promptly returned Any returns should include a note as to the nature of the problem and w...

Reviews: