background image

35 

2.3.1 

Connections 

 

Ensure  that  the  outputs  are  switched  off  and  that  the  device  under  test  is  isolated  before 
making any connections. 

 

Connect  the  main  outputs  as  shown  in  figure  2.3,  selecting  the  most  appropriate  ammeter 
range for the device under test. 

 

Set the phase select switch to trigger the timer on the desired phase. 

2.3.2 

Test procedure 

 

Set the output controls to zero (anti-

clockwise) and the timer mode to “OFF”. 

 

Switch on the main output, and increase the outputs to the desired level. 

 

Switch off the main output. 

 

Switch the timer to “CURRENT OPERATED” mode, and reset the breaker if it has tripped. 

 

Switch the main output on.  The timer will start when current starts flowing in the device under 
test, and will stop when the device trips. 

2.3.3 

Devices with short trip times 

 

 

When  testing  devices  with  short  trip  times  (such  as  thermal  circuit  breakers  at  high  over-
current factors), setting the current may cause the breaker to trip.  In such circumstances, set 
the current using pulse mode.  In this mode, current will be injected for 500ms and the current 
logged 

every time the “ON” button is pressed.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 200A-3PH mk2

Page 1: ...t 3 Phase Secondary Injection Test Set Type 200A 3PH mk2 DESIGNED AND MANUFACTURED BY T R Test Equipment Limited 15 16 Woodbridge Meadows Guildford Surrey GU1 1BJ United Kingdom Telephone 01483 207428...

Page 2: ...ation before making connections to any terminal It is ESSENTIAL to consult the product manual for rating information before making any connection to a terminal or terminal group marked with a warning...

Page 3: ...s if not carried out correctly and may cause damage to the equipment or connected equipment WARNING This action or procedure may be cause injury or death to the operator or other personnel if not carr...

Page 4: ...4...

Page 5: ...phase loads with isolated elements 16 1 3 5 Current Metering 16 1 3 6 Auxiliary AC Voltage Output 17 1 3 7 Auxiliary Metering Input 17 1 3 8 Voltage Measurement 18 1 3 9 Current Measurement 18 1 3 10...

Page 6: ...th DVS3 mk2 voltage source 36 2 4 1 Connections 37 2 4 2 Test procedure restraint angle 37 2 4 3 Test procedure overcurrent timing 38 3 MAINTENANCE 39 3 1 Regulator Brushes 39 3 2 Removal of the 200A...

Page 7: ...ion Resistance at 1000V DC 46 6 2 Applied Voltage Test 46 6 3 Accuracy of Instrumentation and associated circuit components 46 6 3 1 Main Output Ammeter 46 6 3 2 Auxiliary Metering 46 6 3 3 Timing Sys...

Page 8: ......

Page 9: ...allowing a wide range of output configurations to be selected A single phase isolated auxiliary AC output of 110Vac is also available The unit also has an auxiliary metering input with a fast capture...

Page 10: ...ase 110V isolated output K M Main output controls Control main current output level N O Main output on off controls Adjust Knob Switches the main outputs on off Access results and clock settings P Dis...

Page 11: ...the unit is connected to an appropriate supply by a suitably rated connector 1 2 2 Supply Requirements The 200A 3PH mk2 requires a three phase 4 wire 50 60Hz supply of 400V 10 The maximum power requi...

Page 12: ...ot operate from a three wire supply without the optional 200A DSU delta star converter It is essential that this unit is earthed Figure 1 1 Connections for mains input socket 1 2 3 1 Operation from a...

Page 13: ...the three phase mains supply The phase difference between the outputs is therefore fixed Each of the main outputs allows voltage output of 0 5 Vac The ratings are shown in the table below Voltage rang...

Page 14: ...minute on 15 minutes off The complete curve for intermittent current ratings is shown in figure 1 3 Figure 1 3 200A 3PH mk2 maximum on times 1 3 2 Output Phase Relationships The phase relationship be...

Page 15: ...rrents are equally valid Delta output connections are not valid 1 3 3 Star connected loads The configuration and interconnection of the outputs depends on the configuration of the load The configurati...

Page 16: ...re 1 6 Figure 1 6 Connections for load with isolated elements 1 3 5 Current Metering The main output currents are metered by a true RMS reading digital memory ammeter The following ranges are availabl...

Page 17: ...ntly of the main output The voltage and current from this output may be metered using the auxiliary metering input 1 3 7 Auxiliary Metering Input The 200A 3PH mk2 has an auxiliary metering input which...

Page 18: ...t To measure current connect to the COM and 10A aux metering sockets The aux metering rotary switch selects the reading type 1 3 10 Frequency Measurement The frequency of the input signal may be measu...

Page 19: ...hange timer stop 2 Contacts 1st change C2 C2 change C1 change Output cycles on and off Multiple auto re close timing Current Operated Phase Select Current 20 of range Current 20 of range Current 20 Ti...

Page 20: ...Timer mode OFF In the off mode the timer has no effect on the operation of the set and the timer does not run This mode is used to set the required current through the test object before a timing test...

Page 21: ...e re close actions on an auto re closing relay 100 time results can be stored and logged to the USB memory key The auto re close relay breaker trip contacts are connected to contact set C2 and the bre...

Page 22: ...and the output switches off automatically At the end of the test the ADJUST knob is automatically put into timer result selection mode both LEDs off The ADJUST knob scrolls though the timer results T...

Page 23: ...ange in the ADJUST knob will refresh the display to show the selected metered value 1 3 13 7 Timer mode CURRENT OPERATED Current operated mode is used to time devices that have contacts in series with...

Page 24: ...1 14 Normal values displayed on screen 1 4 2 Warning Messages In addition to the normal display screens the 200A 3PH mk2 can display a range of warning messages if the unit trips on over current or d...

Page 25: ...sheet file whenever the timer stops or the output is switched off This is useful for recording all results plotting relay curves and plotting transformer magnetisation curves Files are stored on the U...

Page 26: ...ting the clock Set the STORE RESULT switch to OFF 1 5 1 3 Entering a comment Each result is tagged with a comment when it is stored The comment is entered by setting the store result control to commen...

Page 27: ...If results are to be stored not dependant on the timer set the timer mode to internal start and press the OFF button for the main output when a result is to be stored Results are not stored when the...

Page 28: ...rrent and waveform results files Refer to the instructions in the 200A 3PH mk2 tools spreadsheet for further details Waveform file format The waveform file is in CSV comma separated value format The f...

Page 29: ...t Pins 9 10 of the connector are connected when the output is switched on The contact has a rating of 0 34A 110VAC Resistive load 0 22A 110VAC Inductive load An optional accessory T R link contact lea...

Page 30: ...se angle between the 200A 3PH mk2 output current and an externally generated phase shifted voltage The circuit configuration is shown below using a T R Test Equipment DVS3 mk2 voltage source The AUX M...

Page 31: ...relative to the output current from phase A B or C To do this connect the external current to the aux metering com and 10A terminals and switch the mode switch to phase Select the desired reference p...

Page 32: ...shbutton is pressed and the time the relay trips Figure 2 1 Connections for testing over current relays 2 1 1 Connections Ensure that the output is switched off and that the relay is isolated before m...

Page 33: ...he output will be switched off automatically 2 2 Timing of Auto Reset Reclosing Devices Auto reclosing devices require that the timer is started when power is removed from the device and the timer sto...

Page 34: ...trips The timer will stop when the relay auto recloses 2 3 Timing Circuit Breakers Testing CBE s MCB s and other devices with no auxiliary contacts is possible using the current operated timer mode o...

Page 35: ...and increase the outputs to the desired level Switch off the main output Switch the timer to CURRENT OPERATED mode and reset the breaker if it has tripped Switch the main output on The timer will star...

Page 36: ...se locking between a 200A 3PH mk2 and a DVS3 mk2 may be simplified considerably using the T R link phase locking lead as shown in figure 2 5 Figure 2 5 Connections for directional overcurrent relay us...

Page 37: ...2 Test procedure restraint angle Set the output controls to zero anti clockwise and the timer mode to off Switch on the main output and increase the output current for each phase to the setting curre...

Page 38: ...onal overcurrent relay Set the phase angle so that the relay is not in restraint Set the 200A 3PH mk2 timer mode to OFF Press the 200A 3PH mk2 ON pushbutton and increase the desired test current for e...

Page 39: ...membered that damage to the regulator can result if the brushes are allowed to wear away to such an extent that a loss of brush pressure occurs Figure 3 1 Regulator brush 3 2 Removal of the 200A 3PH m...

Page 40: ...rrent input 4 2 Standard Accessories Supplied a Mains input lead b 3 off 5m 25mm2 blue output leads c 1 off 5m 25mm2 grey output lead d 1 off 5m 25mm2 black output lead e 1 off 5m 25mm2 brown output l...

Page 41: ...0A 3PH mk2 to be used where only a three wire three phase supply is available It also allows operation of the unit from 115V 230V and 400V line line supplies An auxiliary single phase output is provid...

Page 42: ...ctor keyswitch Input voltage selector switch K Mains on off indicator Lit when power is on L Mains on off switch Isolate unit from mains 5 1 2 Electrical Specification 5 1 2 1 Supply Requirements The...

Page 43: ...tput is provided to supply the DVS3 mk2 Do not connect any other type of equipment to this output Voltage 230V 10 single phase Type Single phase isolated from both the mains and three phase outputs Ra...

Page 44: ...Ensure that the supply is switched off Set the supply voltage selector key switch to match the supply voltage SETTING THIS SWITCH TO THE WRONG VOLTAGE MAY DAMAGE THIS UNIT AND ANY EQUIPMENT CONNECTED...

Page 45: ...45 Figure 5 3 Connections between units 3 WIRE SUPPLY OPTIONAL T R LINK LEAD...

Page 46: ...Output Ammeter Range Resolution Accuracy Trip current 20 00A 0 01A 0 6 rdg 5d 21 0A 50 00A 0 01A 0 6 rdg 5d 52 5A 100 0A 0 1A 0 6 rdg 5d 105A 200 0A 0 1A 0 6 rdg 5d 210 0A 6 3 2 Auxiliary Metering Ran...

Page 47: ...47 7 REVISION Product Type Secondary Current Injection Test Set 200A 3PH mk2 File 200A 3PH mk2 manual v3 doc Author JTW Issue Date 3 24 02 17 Modified By K Mupotsa Checked By G Biggs Date 30 05 17...

Page 48: ...48 8 DRAWINGS REQUIRED A2 001947 latest issue 200A 3PH mk2...

Reviews: