23
To view the timing results press the left button to scroll through the stored time values.
Turn AUX AC ADJ clockwise
Figure 1.12 Displaying results for multiple auto-reclose timing
Note:
The auxiliary metering value displayed is dependent upon the position of the auxiliary metering
mode select knob. For example, when the knob is set to PHASE, change in the ADJUST knob
will refresh the display to show the selected metered value.
1.3.13.7 Timer mode: CURRENT OPERATED
Current operated mode is used to time devices that have contacts in series with the current
sense element. This includes miniature circuit breakers and MCCBs.
The timer is started when the output current exceeds 20% of full scale of the selected
metering range, and stops when the current falls below this threshold.
Figure 1.13 Current operation knob selections
0.00A 0.00A 0.00A
0.0V t10 0.08s
0.00A 0.00A 0.00A
0.0V t0 0.300s