082406-40
TC36.CSTE 17
Fig. # 37
HORIZONTAL
TERMINAL
TCVT.9360
14 1/2" FRAMED
OPENING
* Minimum height from the fl oor to center of the
opening with a maximum horizontal run of 32 1/2"
from the center of the fl ue outlet to the outside
face of the outer wall. The height will need to be
increased with longer horizontal pipe
WALL SHIELD
THIMBLE
TCVT.THIMA
24" VENT PIPE
TCVT.811X24
90° ELBOW
TCVT.811XLB90
12" VENT PIPE
TCVT.811X12
Vent pipe:
Install vent pipe through the wall thimble and attach to fl ue
outlet collar on top of the fi replace. Secure all joints with
screws and seal with approved "High Temp." self-adhesive
aluminum tape provided.
The fi replace position may need to be adjusted to ensure
that the vent pipe does not protrude beyond the outer wall
or be recessed any more than 12 inches.
Wall vent terminal:
1) Engage the 8" vent collar with the vent pipe and slide
terminal into place. Attach the terminal to the outside
wall.
The vent terminal must not be recessed into the
exterior wall or siding.
2) Caulk in place to prevent any moisture entering the
building.
NOTE: MINIMUM CLEARANCES TO THE VENT TERMINAL
MUST BE MAINTAINED (see Fig. #45).