Alarm (Basic action)
Alarm sound (buzzer)
(1) Operation
(2) Mode setting
Alarm memory
6
OPERATION AND FUNCTION
SET
ON
OFF
AUTO
(ON)
OFF
Application and installation
●
For the quick detection of the
fl
ame of lighter / match at no
smoking zone.
●
When above setting is not stable.
●
For the detection of the
fi
re at
smoking zone
●
At the window etc. which is
subject to re
fl
ection of sunlights.
SET
The following setting is about detection performance.
Detection sensitivity is selectable STD or L.
(STD: Standard setting: Same sensitivity as previous model)
Detection Sensitivity
SET
Timer
0.2 sec
1sec
6 sec
30 sec
(Factory set : 0.2 sec)
Detection timer
SET
L (50%)
SET
STD (100%)
4 5
Mode selector
1 2 3 4 5
Detection Sensitivity
Alarm Sound
Alarm Memory
Detection timer
1
2
(Factory set : ON)
(Factory set : AUTO)
(Factory set : STD)
3
This product alarms only by detecting the flame continuing
for the set time of detection timer.
(0.2sec., 1sec., 6sec., 30sec.)
When the flame continues further, the above alarm actions
are also continued for the meantime. 2sec. after the flame
goes out, alarm output stops, and 10sec. after, alarm sound
and LED stop (off delay).
Then sensor goes back to armed mode.
FS-2000E is equipped with 4 functions which can be used
according to the application or environment.
Mode setting will be done by mode selector (dip switch) in
accordance with mode setting chart on the back side of
sensor unit.
Installation hole
approx. 5mm
Marking
Installation hole
This product is equipped with installation holes (pitch 3.29" or 83.5mm) to make
installation easy and the sensor's direction adjustable.
Buzzer : Sounds intermittently every 0.2sec.
LED : Lights on
Alarm output : Continuous
To reset the sensor LED which is blinking or lighting on,
Detach sensor unit from base unit and attach it again, or
put off power and on again. (Power on reset)
When the ultraviolet rays of a flame is weak (it is related to
size of flame and distance to sensor), alarm initiation may be
delayed beyond the set time.
The ultraviolet rays are not visible, and may be detected from
unexpected object.
When the sensor's operation is not stable (it detects something
but not a flame) and its cause can not be identified, set
detection time longer by one step and see the course.
Buzzer can be off by mode selector No.1, when external
output is used.
When 2 or more sensor are connected on 1 loop, which
sensor is initiated can be monitored by Memory LED
(yellow) for 50 min. after alarm output. Memory LED
will be off automatically after 3 min. of blinking and 47
min. of lighting on.
In case that the sensor initiates alarm again while its
memory LED is lighting, LED continues to light on for
further 47 min. after that. (re-trigger action)
[Installation of base]
×
×
Place the base on the site and
mark
×
on 2 points 180
°
apart.
Thrust the 2 pcs. of tapping
screws (accessory) leaving 5mm
exposed from the surface.
Adjust the sensor's direction
by turning the base.
(adjustment range 25
°)
(4) Tighten the screws.
●
Installation hole
(1)
(2)
(3)
※
※
(
(
This unit detects ultraviolet rays in a flame and issues a
signal.
In the semi-outdoors, there are many objects which
generate ultraviolet rays and because there are no walls
or windows in open area, there is a much higher possibil-
ity for the unit to detect those objects, in comparison with
indoor installations.
The detection performance should be set using the dip
switches according to the circumstances of the installa-
tion site.
When the performance of the installed sensor is unstable
and the cause cannotbe indentified, select Sensitivity "L"
and detection time one step longer than current setting.
*
Detection distance on "L" setting is 50% shorter than that on
"STD" setting.
*
If the operation is unstable on "STD", switch to "L".
*
When installed semi-outdoor, "L" setting is recommended.
An alarm output occurs when the flame continues for set time of
detection timer or longer.