background image

1. Turn power on.

2. Ignite a lighter etc. within detection area for more than the set time.

3.  After the set time, an alarm output is issued, buzzer sounds intermittently and 

LED blinks. (Alarm action)

4. 2 sec. after the flame goes off, alarm output ends. 10sec. after the flame 

goes off, other alarm actions ends. (Check the alarm output by connecting 
a device such like bell / siren.)

Do not use a lighter in no fire 
zone because it is dangerous.
In such case, operation test 
have to be done in other place 
with sensor only.

Detection area spreads out in 

front of the sensor at approx. 
120

°

conically.

Area locking screw have to be 
turned with a big cross driver 
until the inside of Lock window 
changes to complete black 
(FIXED : turn to right) or white 
(LOOSENED : turn to left).

Sensor installation surface can be covered by the 
most forward area setting.

After the adjustment, detach the sensor unit. 
Fix the sensor head by turning Area locking screw to 
right, and attach it again.

When improper area setting is found out by 

operation check, adjust area setting.

The size of detection area is in 
proportion to the size of flame 
and the time of flaming.
The bigger flame becomes or 
the longer flame continues, the bigger detection area becomes.
When small flame such like lighter's is the object to be detected, 
confirm detection area.

Detection area

Approx. 120°

30°variable

10' (3m)

10' (3m)

20' (6m)

20' (6m)

30' (9m)

30' (9m)

33' (10m)

33' (10m)

30

°

variable

4 steps

7

DETECTION AREA

9

TROUBLESHOOTING

8

OPERATION CHECK

20'

(6m)

23'

(7m)

20'

(6m)

23'

(7m)

23'

(7m)

20'

(6m)

23'

(7m)

20'

(6m)

10'

(3m)

10'

(3m)

10'

(3m)

10'

(3m)

Solve possible problems according to the following table .
If normal operations can not be restored by these corrective actios, contact either 
the dealer from whom you bought the unit or TAKEX.

Trouble  

Completely inactive 

Sometimes inactive 

Activated without 
flame 

The alarm LED and    
buzzer works but the 
connected devices are
inactive

Check 

No power supply (Broken wire or improper wire) 

Low voltage (When power supply wired)

Sensor inside is wet by condensation etc. 

Interrupting rays objects in front of detection area 

  (Glass, transparent resin are interrupting rays objects)

Improper area setting  

Low voltage 

Detection window is soiled with dust 

Large electrical noise source such as a redio station or     

  high-voltage wire nearby

Sensor inside is wet by condensation etc.

Unexpected ultraviolet rays nearby (Ref : 2, ATTENTION)

Poor contact output connection or broken wire  

The connected unit's trouble                        

Relocate the sensor to appropriate position

Correct power supply

Remove the dust and soil

Relocate the sensor

Dry out sensor inside, and remove the cause of wet

Remove the origin of the ultraviolet rays, 

   interrupt ultraviolet rays, or relocate the sensor

Check the wiring or connection

Check the connected unit

Correct power supply or replace broken 

   wire

Dry out sensor inside, and remove the 

   cause of the wet

Remove the interrupting rays object

 Corrective action

  Side view : Ceiling / wall mount

To be fixed

To be loosened

Area locking screw

Lock window

 Front view : Ceiling mount
 Top view   : Wall mount 

Condition of detection area
Detection timer :  0.2sec.
Origin of flame  : Gas lighter
Size of flame     : Approx. 2.75" (7cm)

固 定

1. DETECTION AREA

2. AREA ADJUSTMENT

LOOSENED

FIXED

Lock window

Lock window

Lock window

Adjustment range

Horizontal 25

°

 

………………

By base unit

Vertical 30

° 

(4 steps) 

………

By sensor head

sensor head

Reviews: