Installation
Installation Manual
-Vent termination clearances-
H
D
E
L
B
V
V
V
V
B
F
C
B
B
B
V
V
V
V
V
X
X
A
J
M
Operable
Fixed
closed
Fixed
closed
Operable
B
Inside corner
detail
G
A
K
V
X
= Vent terminal
= Air supply inlet
= Area where the terminal
is not permitted
Regulator/Gas meter
vent outlet
I
Canada Installations
1
US Installations
2
Direct-vent
Direct- vent
A Clearance above grade, veranda, porch, deck, or balcony
1 ft (30 cm)
1 ft (30 cm)
B Clearance to window or door that may be opened
3 ft (91 cm)
1 ft (30 cm)
C Clearance to permanently closed window
0
0
D
Vertical clearance to ventilated soffit located above the
vent terminator within a horizontal distance of 2 feet
(61cm) from the center line of the termination
3 ft (91 cm)
3 ft (91 cm)
E Clearance to unventilated soffit
3 ft (91 cm)
3 ft (91 cm)
F Clearance to outside corner
2 ft (61 cm)
2 ft (61 cm)
G Clearance to inside corner
2 ft (61 cm)
2 ft (61 cm)
H Clearance to each side of center line extended above
meter/regulator assembly
3 ft (91 cm)
*
I
Clearance to service regulator vent outlet
Above a regulator within 3 ft
(91 cm) horizontally of the verti-
cal center line of the regulator
vent outlet to a maximum verti-
cal distance of 15 ft (4.5 m)
*
J Clearance to non-mechanical air supply inlet to build-
ing or the combustion air inlet to any other appliance.
3 ft (91 cm)
1 ft (30 cm)
K
Clearance to mechanical air supply inlet
6 ft (183 cm)
3 ft (91 cm) above if within
10 ft (3 m) horizontally.
L Clearance above paved sidewalk or paved driveway
located on public property
7 ft (213 cm)**
7 ft (213 cm)
M Clearance under veranda, porch deck, or balcony
1 ft (30 cm)***
1 ft (30 cm)***
*Clearance in accordance with local installation codes and the requirements of the gas supplier.
**A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and
serves both dwellings.
***Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Notes:
1)
In accordance with the current CSA B149.1,
Natural Gas and Propane Installation Code
2)
In accordance with the current ANSI Z223.1/NFPA 54
, National Fuel Gas Code