Coral IPx 500 Installation Manual
General System De
script
ion and Installation
1
Above the Cage
The Coral IPX 500 cage requires a minimum space of 2U (3.5" or 89mm) above the top
decorative panel, in order to allow room for maintenance purposes (that is, opening
the top cover, and routing the cables via the rear slots). This cover must be installed at
all times during operation. The open slots on the rear panel allow the cables to be
routed to the top section of the cage. The top cover ensures that the champ cables do
not slip out of the cage. See
Below the Cage
If the customer’s equipment is positioned below the IPx 500 cage, a minimum space of
1U (1.75" or 45mm) must be maintained to allow cool ambient air to reach the
perforations at the bottom panel. See
Fire Hazard! Exceeding the maximum allowed temperature could result in fire. The
Manufacturer’s maximum recommended ambient operating temperature (TMRA) is
104° F (40° C). Ensure that the ambient air temperature around the cage does not
exceed the maximum temperature.
Fire Hazard! Exceeding the maximum allowed temperature could result in fire.Ensure
that a free space of at least 1U (1.75" or 45mm) below the bottom panel of the cage be
maintained to allow the inflow of cool ambient air to the cage.
Fire Hazard! Exceeding the maximum allowed temperature could result in fire. If the
customer’s equipment is installed below the Coral IPx 500, ensure that the temperature
in the space between the Coral IPx 500 and the customer’s equipment does not exceed
122° F (50° C).
Summary of Contents for Coral IPx 500
Page 1: ...Quick Installation Guide The flexible way to communicate Coral IPx 500 DRAFT 3...
Page 10: ......
Page 60: ...1 50 Coral IPx 500 Installation Manual General System Description and Installation 1...
Page 70: ...2 10 Coral IPx 500 Installation Manual Main and Expansion Cage Description Coral IPx 500 2...
Page 85: ......