8.4 Indicator lamps troubleshooting.
Lamps Status
Indication
Corrective Action
1
POWER flashes 10
seconds after A/C
startup (with or
without other signal
lamps).
Communication problem.
Check connection between indoor and
outdoor units.
2
POWER,
COMPRES. and
PRESSURE lamps
flash.
TH-1 failure.
Check TH-1 for correct resistance.
Check for proper connection between
TH-1 and indoor unit.
Replace TH-1 if necessary.
3
POWER,
COMPRES. and
IMPEDANCE
lamps flash.
TH-2 failure.
Check TH-2 for correct resistance.
Check for proper connection between
TH-2 and indoor unit.
Replace TH-2 if necessary.
4
POWER lamp
flashes and
PRESSURE is lit,
AIR CON is OFF.
Low Pressure.
Check if the filters are clean.
Check TH-1 & TH-2 for correct resistance.
Check cooling system for normal
operation.
5
POWER and
PRESSURE
lamps flash, AIR
CON is OFF.
High Pressure.
In Heat mode: Check if the evaporator is
blocked (check if filters are clean).
Check TH-2 (in Heating mode) or TH-3
(in Cool mode) for correct resistance.
Check cooling system for normal
operation.
6
FILTER is lit
Filter cleaning.
Clean all filters.
7
POWER &
IMPEDANCE
lamps flash,
COMPRES. Is lit.
Low voltage.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.
8
POWER lamp
flashes,
IMPEDANCE &
COMPRES.
lamps lit.
AIR CON lamp
flashes after A/C
startup.
Voltage failure at startup.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.
Summary of Contents for ANL-100
Page 15: ...SKY 15 4 1 Refrigeration Cycle ANL 100...
Page 16: ...SKY 16 4 2 Refrigeration Cycle AVL 100...
Page 17: ...SKY 17 4 3 Refrigeration Cycle AVL 120...
Page 18: ...SKY 18 4 4 Refrigeration Cycle AVL 140...
Page 47: ...SKY 47 Fig 9 2 Outdoor Unit Case Assembly 1 2 3 4 5 6 7 8 9 14 16 17 18 15 10 11 12 13...
Page 51: ...SKY 51 Fig 9 4 Outdoor Unit Electrical Components 1 2 3 4 5 6 7 8 9 10 11 12 13...
Page 53: ......
Page 54: ...EN SKY ANL AVL AVR 100 120 140 V01 R01 JAN 2005...