SKY
-
29
-
7.6.3 Drilling a Hole in the Wall for Drainage and Inter-Unit Connections
•
To make the connections between the indoor and outdoor units, a 70 mm hole should be
drilled for the refrigerant lines, drainage hose and electrical cable passage, through the wall,
as shown in Fig. 7-6.
•
Make sure to drill outwards and downwards, so that the opening in the outside wall is at
least 10 mm lower than the opening on the inside.
•
Route the drainage hose at the bottom of the hole.
•
Fill in the remaining wall hole gap with an appropriate sealant.
Fig. 7-6
7.7 Air Duct Installation
•
The air ducts should be constructed of 0.7-0.8 mm galvanized metal sheet.
•
To obtain optimal results, dust cross sections, connections, elbows and branches must be
properly designed. We highly recommend seeking for expert advice on this matter.
•
Air ducts should be properly insulated (preferably on the inside) with 50 mm thick
fiberglass insulation having density of at least 24 Kg/m
3
.
•
See Fig. 7-7 for general guidelines.
Fig. 7-7
70 mm
I NDOOR
OUTDOOR
OUTDOOR SENSOR
REFRIGERANT
ELECTRI CAL
DRAI NAGE
CABLE
LINES
CABLE
TUBE
10 mm. Min
CONCRETE
SLEEVE
AIR DUCT
RUB BER
DRAIN HOSE
AIR INTAKE G RILL
CEILING
2 min
CEILING
CUS HION
CONNE CTION
Summary of Contents for ANL-100
Page 15: ...SKY 15 4 1 Refrigeration Cycle ANL 100...
Page 16: ...SKY 16 4 2 Refrigeration Cycle AVL 100...
Page 17: ...SKY 17 4 3 Refrigeration Cycle AVL 120...
Page 18: ...SKY 18 4 4 Refrigeration Cycle AVL 140...
Page 47: ...SKY 47 Fig 9 2 Outdoor Unit Case Assembly 1 2 3 4 5 6 7 8 9 14 16 17 18 15 10 11 12 13...
Page 51: ...SKY 51 Fig 9 4 Outdoor Unit Electrical Components 1 2 3 4 5 6 7 8 9 10 11 12 13...
Page 53: ......
Page 54: ...EN SKY ANL AVL AVR 100 120 140 V01 R01 JAN 2005...