General Troubleshooting (continued).
Symptom
Probable Cause
Corrective Action
15
Outdoor fan is not
running at all.
1. Power
supply
failure..
2. Fan motor relays failure.
3. Fan contactor failure.
4. Motor winding failure
(check resistance).
1. Check
power
supply.
2. Replace
faulty
relays.
3. Replace
faulty
contactor.
4. Replace the fan motor.
16
Compressor motor
is not running at all
1. Failure in compressor
motor magnetic contactor.
2. Failure in KP-5.
3. Compressor
motor
winding
failure (check resistance).
1. Replace
faulty
contactor.
2. Reset
KP-5.
3. Replace
the
compressor.