2.3
Safety equipment
2.3.1
Safety equipment installed
2.3.1.1
Main shut off valve
2) are used to shut off the primary heat circuit.
Shut the ball valve in the event of a fault. The ball valve is shut off
once the handle is horizontal. If it is not clear which ball valve needs
to be shut off, shut off all ball valves.
The slow-closing piston valve (Fig.
3) is used to shut off the drinking
water circuits at the connection points. In the event of a fault, turn
the handle clockwise as far as it will go. If it is not clear which piston
valve needs to be shut off, shut off all piston valves.
2.3.1.2
Safety DCW valve (Option)
4) depressurises the station in the event of
excess pressure on domestic cold/hot water site. The safety valve is
calibrated for a pressure of 10
bar and does not need to be set during
commissioning.
A pressure relief line must be connected to the safety valve during
Chapter 5.3.2 ‘Connecting the pressure relief line to
36).
Ball valves
Fig.
2:
Ball valve
Piston valve
Fig.
3:
Piston valve
Fig.
4:
Safety DCW valve
TACOTHERM FRESH PETA 2 / PETA 2 X
Safety
V02.2020 11/2020
Item no. 215747
EA no. 1329
Operating instructions
12