11
Mixing Target Temperature
The Mixing Target Temperature sets the desired supply temperature when operating in
the setpoint mode. This item is only available if the Outdoor Design setting is set to OFF.
V
Mixing Return Temperature
The mixing return temperature is displayed when the MIX RET elements are turned on.
This is the current temperature at the mixing return sensor. The mixing return temperature
is only displayed if the Outdoor Design temperature is turned OFF and a mixing return
sensor is installed.
Mixing Target Temperature
The mixing target temperature is displayed when the MIX TARG elements are turned on.
This is the temperature the RMC is currently trying to maintain at the supply sensor.
If “- - -” is displayed, the RMC is either in WWSD or a demand for heat is not present.
Boiler Temperature
The boiler temperature is displayed when the BOIL element is turned on. This is the
current temperature at the boiler sensor. The boiler temperature is only displayed if a
boiler sensor is installed.
ADJUST MENU
To switch between the View menu and the Adjust menu, press and release the MENU button on the face of the control. To advance to
the next available Adjust Item, press and release the ITEM button on the face of the control.
O
MIX
DEM
VIEW
F
%
1
RET
MIX
DEM
VIEW
F
%
1
TARG
BOIL
DEM
VIEW
F
%
1
MIX
ADJUST
F
TARG
Delta T Maximum
The Delta T Maximum sets the maximum temperature difference between the mixing
return sensor and the mixing supply sensor. This item is only available if Outdoor Design
setting is set to OFF. If a mixing return sensor is not installed, set this item to OFF.
Outdoor Design Temperature
The Outdoor Design Temperature is the outdoor temperature used in the heat loss calcu-
lation. If the RMB is used in the outdoor reset mode, this item is set to the typical coldest
outdoor temperature. If the RMB is used in the setpoint mode, this item is set to OFF.
Mixing Design Temperature
The mixing design temperature is the supply temperature used in the heat loss calcula-
tion. This is the supply temperature that is required to heat the building when the outdoor
temperature is as cold as the outdoor design temperature. This item is only available if the
Outdoor Design setting is not set to OFF.
Mixing Maximum Temperature
The mixing maximum temperature is the highest temperature that the control is allowed to
use as a mixing target temperature. This item is only available if the outdoor design set-
ting is not set to OFF.
M
T
MAX
ADJUST
F
OUT
ADJUST
F
DSGN
MIX
ADJUST
F
DSGN
MIX
MAX
ADJUST
F
Mixing Minimum Temperature
The mixing minimum temperature is the lowest temperature that the control is allowed to
use as a mixing target temperature. This item is only available if the outdoor design set-
ting is not set to OFF.
B
MIX
MIN
ADJUST
Summary of Contents for Radiant Mixing Block
Page 2: ...2 Typical Piping ...