background image

Application:

The Taco Clock Timer/Temperature Aquastat combination is
designed to cycle the circulator during peak demand peri-
ods. The Analog Timer (No. 265-1) is adjustable to 15 minute
intervals within a 24 hour time frame. The Digital Timer
(No. 265-3) can be programmed for 7 day operation. The
Temperature Aquastat (No. 563-2) automatically switches
the circulator ON at 95ºF and OFF at 115ºF. The two can
be used in combination, or they can be used separately.
When the Clock Timer/Temperature Aquastat are used
together, the Timer switches ON sending power to the unit.
The Temperature Aquastat measures the temperature, and
cycles the circulator as long as the Timer is switched to the
ON mode.

If used separately, the Clock Timer operates the circulator
during the chosen number of ON/OFF intervals. When using
only the Temperature Aquastat, the circulator cycles inter-
mittently to maintain a temperature between 95ºF and 115ºF.

The Clock Timer and Temperature Aquastat are easy to
retrofit to any “00” Series Circulator. The user-friendly 24
hour analog clock has an hour hand, raised minute hand
for ease of adjustment, two directional arrows, and AM/PM
time settings. Our easy to program digital timer provides
maximum convenience, comfort and energy savings. The
Clock Timer can be mounted in any direction by just
attaching it to the capacitor box electrical connection hole.

Installation: FOLLOW ALL INSTRUCTIONS IN THE 

SEQUENCE THAT THEY APPEAR.

Analog Timer Installation Instructions:

1. Disconnect the electrical supply. Remove circulator

terminal box screw and cover.

2. Loosen Timer box cover screw and remove cover.

3. Assemble the back portion of the Timer to the “00” ter-

minal box as shown in the Timer installation diagram
(006 circulator pictured). Make sure that the protruding
tang on the back of the Timer box fits under the circu-
lator’s terminal box base. Adjust until the two terminal
box openings are aligned.

4. Secure the locknuts. Feed the yellow and white circu-

lator lead wires into the Timer through the bushing.
Reassemble circulator terminal box cover and secure
with the screw.

5. See electrical hook-up for Timer wiring.

Aquastat Installation Instructions:

1. Disconnect the electrical supply. Securely fasten the

Aquastat clip to 

3

4

" pipe or to the circulator casing for

1

2

" pipe applications. The Aquastat must be properly

fastened to insure a good reading.

2. See electrical hook-up for Aquastat wiring.

Electrical Hook-Up:

1. All electrical work must be performed by an electrician

in accordance with the latest edition of the National
Electrical Codes and Local Codes and Regulations.

2. Verify that the voltage, phase and frequency are correct

for the Circulator, Timer and Aquastat prior to connection.

3. Follow the appropriate wiring diagram

Analog Timer Programming:

1. Set the clock to the exact time of day using the clock

face minute hand. Pay special attention to the corre-
sponding AM and PM settings.

2. Supply power. Test circulator by pushing Timer lever into

the manual position.

3. Set the desired ON/OFF times in 15 minute intervals.

Push trippers away from clock face for ON operation, and
leave trippers toward the clock face for OFF operation.

Programming Modes:

1. Up = On, Constant

circulation    

I

2. Middle = Automatic

operation

3. Down = Off    O

Instruction Sheet

Timer and Aquastat

102-067

SUPERSEDES: November 15, 1992 

EFFECTIVE: May 1, 2003

Plant ID# 001-979

Analog Timer Clock Face

Summary of Contents for 265

Page 1: ...ew and remove cover 3 Assemble the back portion of the Timer to the 00 ter minal box as shown in the Timer installation diagram 006 circulator pictured Make sure that the protruding tang on the back of the Timer box fits under the circu lator s terminal box base Adjust until the two terminal box openings are aligned 4 Secure the locknuts Feed the yellow and white circu lator lead wires into the Ti...

Page 2: ...ists of 1 An ON or OFF command 2 Time of day Hour and Minute 3 Single day or multiple days A program is required for each ON event and a program is required for each OFF event IMPORTANT BEFORE PRO CEEDING WITH SETTING THE TIME AND PROGRAMMING THE UNIT PRESS THE RESET KEY TO CLEAR ALL DATA FROM MEMORY Selecting AM PM or Military Time After pressing reset the display may show AM right The numbered d...

Page 3: ...cepted Day Key Selections Reviewing Programs To review the programs at any time press Prog key Programs will appear in the order they were entered with repeated presses of the Prog key After all programs have been reviewed the blank display will appear to allow enter ing another program Another press of the Prog key will display the number of free programs available such as Fr 16 if 4 programs hav...

Page 4: ...M A program for 8 AM Monday thru Friday was entered but it will not accept it and is flashing SOLUTION The ON or OFF was not entered as part of the program On or OFF must be selected DO IT ONCE DO IT RIGHT TACO INC 1160 Cranston Street Cranston RI 02920 Telephone 401 942 8000 FAX 401 942 2360 TACO Canada Ltd 6180 Ordan Drive Mississauga Ontario L5T 2B3 Telephone 905 564 9422 FAX 905 564 9436 Visit...