![Taco 00e Series Installation/Operation Instruction Manual Download Page 46](http://html2.mh-extra.com/html/taco/00e-series/00e-series_installation-operation-instruction-manual_3166579046.webp)
-46-
Address
Register name
Range
Resolution
Description
001
Lag Delay
0..10000
1 ms
Delay in milliseconds for lag reply. This delay will be
added to every Modbus reply [default = 0].
002
RESERVED
---
---
---
003
ModbusAddress
1..247
1
Modbus lag/device address [default = 245].
004
BitRate
0..5
1
RS-485 transmission speed enumeration.
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud [default]
5 = 38400 baud
6 = 57600 baud
005.. 008
RESERVED
---
---
---
009
Parity
0..2
1
Parity setting to be used for
communication.
0 = No parity
1 = Even parity [default]
2 = Odd parity
010
StopBits
1..2
2
Stop bits used for communication. 2 stop
bits will only be used when “Parity” is set to 0.
1 = 1 stop bit [default]
2 = 2 stop bits
011
RESERVED
---
---
---
012
Relay1Control
0..2
1
Configures module relay output.
0 = indicates fault
1 = indicates pump ready
2 = indicates pump operation
See section
“Error! Reference source not found. Error!
Reference source not found.”
013
ErrorDelay
0..30
1
Error signal on Relay and register 201.10
will be delayed by ErrorDelay seconds.
Summary of Contents for 00e Series
Page 55: ...55 VR15 L M H VR20 L M H...