-24-
MODE 1 – Digital switched enable / disable (on/off), external analogue 0-10Vdc speed or head control
(pump starts on medium speed or head)
Application: Using an external 0-10Vdc signal to control the speed (or head) of the pump and a separate signal
to enable/disable the motor. Pump starts and stops on medium speed for pre and post purging.
IMPORTANT:
• Mode value must not be set to MAX or Auto, otherwise changes in the 0-10Vdc signal
will not change the pump’s performance
• Minimum and maximum speeds can be set via the pump’s HTML web page “Pump” configuration tab
• Reverse polarity will not cause damage – The pump will not react to any changes
• 0-10Vdc values can be confirmed on the pumps HTML web page, Overview Tab, Control Signal
(
See Section 19
)