![Taco 00e Series Installation/Operation Instruction Manual Download Page 39](http://html2.mh-extra.com/html/taco/00e-series/00e-series_installation-operation-instruction-manual_3166579039.webp)
-39-
17. BACnet
17.1 BACnet MS/TP communication is standard with all VR models
VR Series module enables BACnet MS/TP communication with all models.
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
Name
BACnet BIBB
Read Property
DS-RP-B
Write Property
DS-WP-B
BACnet Interoperability Building Blocks Supported (Annex K):
Name
BACnet BIBB
Who-is/I-am
DM-DDB-A
DM-DDB-B
Who-has/I-have
DM-DOB-B
Device management services:
NOTE: Segmentation is not supported.
NOTE: Dynamically creatable objects are not supported.
17.2 Data Link LAYER Options
MS/TP master (Clause 9), baud rate(s):
Baud Rate
9600
19200
38400 [default]
BACnet IP
(CURRENTLY NOT IMPLEMENTED)
Summary of Contents for 00e Series
Page 55: ...55 VR15 L M H VR20 L M H...