TAC AB, 1999-08-18
0-004-7516-1 (GB), 8:7 (10)
TAC Xenta 102 Handbook
Communication
8.6.2 The controller object’s outputs (nvo)
Index Variable
Hb*
1
SNVT
Accepted values
Default value
Description
(Self doc. string)
1
nvoEffectOccup Yes
SNVT_occupancy
0=OC_OCCUPIED
OC_OCCUPIED Effective occupancy
1=OC_UNOCCUPIED
output
2=OC_BYPASS
@1#3
3=OC_STANDBY
255=OC_NUL
2
nvoUnitStatus
Yes
SNVT_hvac_status
1=HVAC_HEAT
HVAC_HEAT
Unit status output
mode
3=HVAC_COOL
@1|4
9=HVAC_FAN_ONLY
6=HVAC_OFF
heat_output_primary
0% to 100%
163,83%
(
*
2)
163,83%
(
*
2)
heat_output_secondary
0% to 100%
163,83%
(
*
2)
163,83%
(
*
2)
cool_output
0% to 100%
163,83%
(
*
2)
163,83%
(
*
2)
econ_output
163,83%
(
*
2)
163,83%
(
*
2)
fan_output
0% to 100%,
163,83%
(
*
2)
163,83%
(
*
2)
in_alarm
255
(
*
2)
255
(
*
2)
3
nvoAlarmStatusNo
SNVT_state
16 bits, 0=normal,
00000000
Alarm status
1 = alarm
00000000
output, @1#4
4
nvoEffectSetpt
Yes
SNVT_temp_p
10 °C to 35 °C
327,67 °C
(
*
2)
Effective setpoint
327,67 °C
(
*
2)
output,@1|16
5
nvoSpaceTemp Yes
SNVT_temp_p
–10 °C to 50 °C,
327,67 °C
(
*
2)
Zone temperature
327,67 °C
(
*
2)
output, @1|3
6
nvoFlowControl Yes
SNVT_flow
0 to 65534 l/s
0 l/s
Effective flow control
Pt
65534
(
*
2)
output, @1|17
7
nvoBoxFlow
Yes
SNVT_flow
0 to 65534 l/s
0 l/s
Output air flow in
65534
(
*
2)
VAV box, @1|18
8
nvoTerminal
Yes
SNVT_lev_percent –163,84% to 163,84%
0%
Heat./cool. demand
Load
output, @1|19
9
nvoSpaceCO2
Yes
SNVT_ppm
0 to 5000
65535
(
*
2)
ppm
Zone CO
2
sensor
65535
(
*
2)
output, @1#5
10
nvoEnergy
Yes
SNVT_switch
0=Off, 1=On
Off, 0%
Energy hold off
HoldOff
0% to 100%
output
Off, 0% = no delay
@1|20
11
nvoFlowSetpoint Yes
SNVT_lev_percent 0% to 100%
0%
Flow setpoint output
@1#6
12
nvoHeatSlave
No
SNVT_switch
0=Off, 1=On,
0 %
Heating control out-
0% to 100%
put for slave; @1#2
42
nvoOccSensor
Yes
SNVT_occupancy
0=OC_OCCUPIED
OC_NUL
Occupancy sensor
1=OC_UNOCCUPIED
output
255=OC_NUL
@1#27
*
1
Hb=Heartbeat
*
2