8:6 (10), 0-004-7516-1 (GB)
TAC AB, 1999-08-18
TAC Xenta 102 Handbook
Communication
8.6.1 The controller object’s inputs (nvi)
Index Variable
Hb*
1
SNVT
Accepted values
Default value Description
(Self doc. string)
13
nviManOccCmd No
SNVT_occupancy
0=OC_OCCUPIED
OC_NUL
Occupancy
1=OC_UNOCCUPIED
scheduler input,
3=OC_STANDBY
@1|8
other values=OC_NUL
255=OC_NUL
14
nviApplicMode Yes
SNVT_hvac_mode 0=HVAC_AUTO
HVAC_AUTO Application mode
1=HVAC_HEAT
input, @1|5
3=HVAC_COOL
4=NIGHT_PURGE
6=HVAC_OFF;
all other values
interpreted as
HVAC_AUTO
15
nviSpaceTemp Yes
SNVT_temp_p
–10 °C to 50 °C,
327,67 °C
(
*
2)
Zone temperaure
327,67 °C
(
*
2)
input, @1|1
16
nviSetpoint
No
SNVT_temp_p
10 °C to 35 °C,
327,67 °C
(
*
2)
Temperature
327,67 °C
(
*
2)
setpoint input, @1|2
17
nviSetpntOffset Yes
SNVT_temp_p
–10 °C to 10 °C
0 °C
Setpoint offset
input, @1|7
18
nviSpaceCO2
Yes
SNVT_ppm
0 to 5000 ppm
65535*
2
ppm
Zone CO
2
input,
65535*
2
@1|13
19
nviEnergyHold Yes
SNVT_switch
0=Off, 1=On,
Off, 0%
Energy hold off
Off
0% to 100%
input. Enabled
at 1=On and
≠
0%
@1|11
20
nviManOverride No
SNVT_hvac
0=HVO_OFF
HVO_OFF
VAV manual over-
_overid
1=HVO_PERCENT
ride input
state
2=HVO_FLOW
@1|6
percent
other values=HVO_OFF
flow
21
nviEmergCmd
No
SNVT_hvac
0=EMERG_NORMAL
EMERG_
Emergency com-
_emerg
1=EMERG_PURGE
NORMAL
mand input
2=EMERG_SHUT-
@1|9
DOWN 3=EMERG_
PRESSURIZE
4=EMERG_DEPRES-
SURIZE, other values=
EMERG_NORMAL
22
nviBoxFlow
No
SNVT_flow
0 to 65534
0
Box flow input
@1|10
23
nviHeatSlave
No
SNVT_switch
0=Off, 1=On,
0 %
Heating control
0% – 100%
input for slave
@1#1
43
nviOccSensor
Yes
SNVT_occupancy
0=OC_OCCUPIED
OC_NUL
Occupancy sensor
1=OC_UNOCCOUPIED
input
other values=OC_NUL
@1#28
*
1
Hb=Heartbeat
*
2
Off value