SRC-131 Hotel Controller Manual
18
40017
Read / Write
Relay Span
0.5°C to 3.0°C in 0.5°C Steps
1°F to 10°F in 1°F Steps
Value / 10 (e.g. 1.0°C Span = 10)
40018
Read / Write
Fan Purge Period 0 = Off
1 = Fan Purge - 1 Min
2 = Fan Purge - 3 Min
3 = Fan Purge - 5 Min
4 = Fan Purge - 10 Min
5 = Heat Only Fan Purge - 1 Min
6 = Heat Only Fan Purge - 3 Min
7 = Heat Only Fan Purge - 5 Min
8 = Heat Only Fan Purge - 10 Min
9 = Cool Only Fan Purge - 1 Min
10 = Cool Only Fan Purge - 3 Min
11 = Cool Only Fan Purge - 5 Min
12 = Cool Only Fan Purge - 10 Min
40019
Read / Write
0-10V Heat Span 0.5°C to 3°C in 0.5°C Steps
1°F to 6°F in 1°F Steps
Value / 10 (e.g. Heat Span of 1°C= 10)
40020
Read / Write
0-10V Cool Span
0.5°C to 3°C in 0.5°C Steps
1°F to 6°F in 1°F Steps
Value / 10 (e.g. Cool Span of 1°C = 10)
40021
Read / Write
Auto Off Timer
0 = 0ff
1 to 10 Hours.
Value / 10 (e.g. 3 Hour Auto Off Timer = 30)
40022
Read /Write
Unoccupied Heat
Set Point
0 = Off
5°C to 30°C in 0.5°C Steps
41°F to 86°F in 1°F Steps
Value / 10 ( e.g. 17°C Unoccupied Heat = 170)
40023
Read / write
Unoccupied Cool
Set Point
0 = Off
5°C to 30°C in 0.5°C Steps
41°F to 86°F in 1°F Steps
Value / 10 ( e.g. 28.5°C Unoccupied Cool =
285)
40024
Read / Write
Unoccupied Fan
Mode
3 Fan Speed Mode
1 = Low (Fan Auto)
2 = Med ( Fan Auto)
3 = High (Fan Auto)
4 = Low (Fan On)
5 = Med (Fan On)
6 = High (Fan On)
1 Fan Speed Mode
0 = Fan Auto
4 = Fan On
40025
Read / Write
Backlight
0 = On With Button Press
1 = Always On (High)
2 = Always On Low - High With Button Press
40026
Read / Write
Remote
Temperature
Input Function
0 = Replace On Board Sensor With Remote
1 = Average Onboard Sensor With Remote
2 = Modbus Use Only (e.g. Coil Temp
Monitor)
40027
Read / Write
Digital Input
Function
0 = Occupancy Initiate
1 = Chime Door Bell
40028
Read / Write
Reset Fan Mode
0 = Leave Fan Mode Unchanged
1 = Reset Fan To Auto At Switch Off
40029
Read / Write
Belimo Mode
0 = Standard 0-10V Valve Logic
1 = Belimo 6V = Off 3 Way Valve Logic
40030
Read / Write
Modbus Address
1 to 255
40031
Read / Write
Baud Rate
1 = 4.8Kbs
2 = 9.6kbs
3 = 19.2Kbs
40032
Read Only
Digital Input
Status
0 = Open
1 = Closed
40033
Read Only
Internal Sensor
Value / 10 (e.g. 23.3°C = 233)