SRC-131 Hotel Controller Manual     

10

 

 
 
 
 

5.4 

Fault Indication 

The SRC-131 can display the text “FLt” alternating with the temperature should you wish to alert the user of an 
external fault with the heating or cooling system. 

 

To enable  this function enter the installer menu and set the Window contact  input setting 31 to option 3.  (See 
page 16 for this setting). When the WC terminal and the Com-0V terminal are joined the SRC-131 will alternate 
“FLt” with the current room temperature. 

 

Register 32 will permit a time delay to be set after the fault signal is received if necessary to reduce false trips. 

 

The fault indication has NO effect on thermostat function 

 

5.5 

Door Switch 

The Door switch input (DS) is used by the SRC-131 for 3 functions. 
1) 

To detect that the door has been opened and then closed to let somebody into or out of the room. 

2) 

To detect if the door has been left open. 

3) 

To use as an occupancy or Auto-Off timer in training rooms or similar. 

 

The SRC  door switch  input  can  be set  for a  Normally  Open  (switch  open  when  door  is  closed)  or normally 
closed  logic  (switch  closed  when  door  is  closed)  or  OFF  (input  not  used).   The  Installer menu 30 “Door Input 
Logic” and option 31“Door Input Delay” sets the door detection logic in the SRC-131. 
 

5.6 

Entering or exiting the room. 

Once the door is opened and then closed the SRC-131 will begin its occupancy detection process using the PIR 
input  described  below.  Based  on  the  outcome  of  this  process  the  SRC-131  will  remain  on  and  permit  guest 
interaction  with the SRC-131  (adjust mode and  set point for  example),  or switch to “un-occupied” mode where 
the SRC-131 will substitute the guest set point and mode for the installer pre-set values. 
 

5.7 

Door Left Open 

When the door is  left  open for longer than  the pre-set time  (0 to 300  seconds) the SRC-131  will automatically 
turn OFF. The text “OFF” will flash in the display to indicate that the remote door (or window switch) is holding 
the SRC-131 in off mode. This is done to prevent energy waste by trying to heat or cool an open room. 

 

The SRC-131 will automatically restart once the door is closed. 
 

5.8 

PIR input 

A PIR (passive infra-red) movement detector can be directly wired to the SRC-131 “PIR” input. As movement is 
detected  by  the  PIR  it  will  send  multiple  On/Off  pulses  to  the  SRC-131  every  time  it detects  movement.  The 
SRC-131  using  this  data  along  with  door  switch  data  will  determine  the  occupancy  status  of  the  room  and 
behave accordingly.  Note, the PIR must be separately powered, typically from a 12VDC supply. 

 

5.9 

Automatic Occupancy Detection Logic 

Automatic occupancy detection requires the door switch and PIR input to be wired and working. 

 

When the door is first opened the SRC-131 instantly enters “Occupied Mode” where the SRC-131 will permit the 
guest to set their desired temperature and mode of operation. Once the door is closed the SRC-131 will “look” 
for movement as detected by the PIR sensor wired to the PIR input. If no movement is seen within the installer 
pre-set seek  time (installer  adjustable 1  to  15 minutes) the SRC-131  will  enter “Un-occupied mode”  where the 
guest’s  temperature and  mode will be replaced  with  installer  pre-set  values.    Should  movement be  detected 
within  the  installer  pre-set seek  time  the  SRC-131  will  LOCK  into  “Occupied  Mode”  and  no  longer  rely  on 
continued movement within  the  room  to  remain  in  “Occupied  Mode”.  Next  time  the  door  is  opened  and  then 
closed again the SRC-131 will again begin its occupancy detection process. 

 

Note - even when the SRC-131 is in “un-occupied mode” it will continue to use the PIR input to determine room 
occupancy.  For  example  -  a  couple  may  be  staying  in  the  room  and  one  leaves  the  room  leaving  the  other 
asleep  in  bed.  As  the  door  closes  the  SRC-131 will  seek movement  and when  none is found  it will enter “un-
occupied  mode.  As  the sleeper wakes  and  then  moves  the SRC-131 will  automatically  re-enter  “Occupied 
Mode” even though it may have been some time since the door was closed. 

 

Summary of Contents for SRC-131

Page 1: ...SRC 131 Modbus Hotel Room Controller User Manual SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter Devon EX3 0QH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 www syxthsense com...

Page 2: ...ies for which SyxthSense Limited has a right to use The contents are copyrighted and must not be communicated in whole or in part to any other party without the prior written approval of SyxthSense Li...

Page 3: ...8 4 9 BELIMO 6 WAY VALVE 8 4 10 2 PIPE MODE 8 5 WIRING EXAMPLES ANCILLARY FUNCTIONS 9 5 1 COMPLETE SYSTEM OVERVIEW 9 5 2 OCCUPANCY DETECTION 9 5 3 WINDOW CONTACT 9 5 4 FAULT INDICATION 10 5 5 DOOR SWI...

Page 4: ...pending on switch and installer menu settings not all segments maybe shown On Off Tap the On Off button to turn the thermostat On or Off and If permitted to select heat only or cool only mode To ensur...

Page 5: ...temperature sensor 3 4 DIP Switch Settings Switch Function On Off Sw1 Indoor Fan Mode 3 Fan Speed 1 Fan Speed Sw2 Equipment Type Heat Pump Heat Cool Sw3 HP Mode Sw2 ON HC Mode Sw2 OFF Rev Valve Heat B...

Page 6: ...or Switch Monitors room door status for occupancy detection see page 11 PIR PIR Movement sensor input for occupancy detection see page 11 The SRC 131 is powered by 24VAC and requires the 24VAC active...

Page 7: ...s actions The SRC 131 displays the relay actions more than the actions of the 0 10V outputs on the LCD In most cases these are very closely matched however as the 0 10v outputs have the capability of...

Page 8: ...this manual As with normal valves the 0 10V heating and cooling span settings in the installer menu scale the heating and cooling outputs Factory default is full heating and full cooling 1 C from set...

Page 9: ...control conferential HVAC systems 2 or 4 pipe fan coils with modulating valves the SRC 131 has the necessary outputs to achieve your control needs 5 2 Occupancy Detection The SRC 131 has sophisticate...

Page 10: ...The text OFF will flash in the display to indicate that the remote door or window switch is holding the SRC 131 in off mode This is done to prevent energy waste by trying to heat or cool an open room...

Page 11: ...ndicates occupancy status 5 12 Doorbell A built in doorbell feature is included with the SRC 131 controller This is normally activated by the optional door station or via Modbus data link In circumsta...

Page 12: ...additional functions within the SRC 131 controller It also permits all modes functions and controls to be remotely supervised and adjusted from a central location if needed Modbus object data can be...

Page 13: ...nu are 1 Ensure that the controller is OFF 2 Tap top left of the LCD then tap top right of the LCD then press and hold the centre of the LCD for 5 seconds 6 1 Navigating Through The Installer Mode Set...

Page 14: ...span 3 speed relays 0 5C 3 0C 1 0F 6 0F 0 1C 0 1F steps Data format Fan span 10 10 0 10V Fan Interval PI 10 300 seconds 10 seconds steps 60 seconds default 11 0 10V Fan direction 0 0 10V slow to fast...

Page 15: ...ps ver 3 3 changed 0 60min 36 Reset Fan 0 Off 1 On 37 Belimo Mode 0 Off 1 On 38 Modbus Address 1 255 39 Baud rate 1 4800bps 2 9600bps default 40 Default Start Temp Version 3 3 0 OFF default 15 35C or...

Page 16: ...Online Store www syxthsense com Copyright 2016 SyxthSense Ltd Enquiries T 0844 840 3100 F 0844 840 3200 SRC 131 Hotel Controller Manual 16 Holding Registers and entering the address simply as 12...

Page 17: ...Low Speed Ventilation 1 or 3 Fan Speed 2 Med Speed Ventilation 3 Fan Speed Only 3 High Speed Ventilation 3 Fan Speed only 4 Air Conditioning ON 1 or 3 Fan Speed 40008 Read Write Fan Status 3 Fan Speed...

Page 18: ...t 0 Off 5 C to 30 C in 0 5 C Steps 41 F to 86 F in 1 F Steps Value 10 e g 17 C Unoccupied Heat 170 40023 Read write Unoccupied Cool Set Point 0 Off 5 C to 30 C in 0 5 C Steps 41 F to 86 F in 1 F Steps...

Page 19: ...7 3v send 1073 40041 Read Write 0 10V Cool Value Value 10 e g 7 3V 73 To write add 10 e g to write 7 3v send 1073 Values below only apply to version 2 hardware only Firmware version 3 40043 Read Write...

Page 20: ...Colours Available Upon Request Display Type STN Touch Panel Relay Rating 30V 1Amp Max 0 10V Output Load 10mA Max Control Range 5 C to 30 C 41 F to 86 F Memory Type Non Volatile Settings Do Not Requir...

Reviews: