SRC-131 Hotel Controller Manual
14
6.2
Option List Table
Option
Setting
0
Buttons Shown
0: Both mode and fan buttons show (default)
1: Show mode but fan button hidden
2: Show fan but mode button hidden
3: Both mode and fan buttons Hidden
Note: If the mode button is hidden, the service and maintenance
staff can turn the SRC-131 on or off by pressing and holding the lower left of
the LCD for 15 seconds. 2 chirps indicates the SRC-131 has turned ON. 1
chirp indicates the SRC-131 has turned off (ver 3.03+)
1
Permitted Modes
0: Off / Auto
1: Off / Auto / Heat / Cool
2: Off / Heat /Cool
3: Off / Heat
4 Off / Cool
5: Off / Auto (Display current heating or cooling mode)
2
Room / Set display
0: Show room and set temp (default)
1: Show set temp only
3
Native display format
0: C (default) 1: F
4
C/F button shown on LCD 0: Off(default) 1: On
5
High temp set limit
5C-30C/41F-86F
6
Low temp set limit
5C-30C/41F-86F
7
Dead band
0C-5.0C/0F-10.0F 0.1C/0.1F steps
Data format :
Dead band * 10
8
Fan Purge Period
0: OFF
1: Fan purge - 1 min
9
Fan span (3 speed relays) 0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format : Fan span * 10
10
0-10V Fan Interval (PI)
10-300 seconds 10 seconds steps (60 seconds default)
11
0-10V Fan direction
0: 0 - 10V – slow to fast
1: 10 to 0V – slow to fast
12
0-10V Fan minimum value
(minimum
fan
0 -10V
Data format : 0-10V Fan minimum value * 10
13
0-10V Fan Maximum value
(Maximum fan
0 -10V
Data format : 0-10V Fan minimum value * 10
14
Heat span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format : Fan span * 10
15
0-10V Heat interval (PI)
10-300 seconds 10 seconds steps (60 seconds default)
16
0-10V Heat direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open n(reverse acting)
17
0-10V
Heat
minimum
0 -10V
Data format : 0-10V Heat minimum value * 10
18
Cool span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format : Fan span * 10
19
0-10V Cool interval (PI)
10-300 seconds 10 seconds steps (60 seconds default)
20
0-10V Cool direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open n(reverse acting)
21
0-10V
Cool
minimum
0 -10V
Data format : 0-10V Cool minimum value * 10
22
Auto Off Timer
0: No auto off timer
1-10hours 0.5 hour increments. Data format : hour * 10
23
Un-occupied heat
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
24
Un-occupied cool
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
25
Un –Occupied fan mode
Fan 3 Speed mode
1: Low (Auto) (default)