SRC-131 Hotel Controller Manual     

17

 

 
 
 
 

 

6.3.1 

Data Format 

 
Protocol:   

Modbus RTU 

Byte Format: 

1 Start Bit, 8 Data Bits, 1 Stop Bit, No Parity 

Address:   

1 to 255 

Baud: 

 

4800 / 9600 / 19200 BPS 

 

Holding 

Register

 

Type

 

Value

 

Comments

 

40001

 

Read Only

 

Device ID

 

Always Returns “131” 

40002

 

Read Only

 

Firmware Version

 

Divide By 100 (e.g. Version 2.36 = 236)

 

40003

 

Read Only

 

DIP Switch 
Settings

 

Binary Count 
Sw 1 = 1, Sw2 = 2, Sw3 = 4, Sw 4 = 8 etc

 

40004

 

Read / Write

 

Occupancy Status

 

0 = Room is Unoccupied 
1 = Room is Occupied 
Note - Modbus can write “0” holding the 
room unoccupied regardless of the occupancy 
input. 
Modbus  cannot  override  the  occupancy  input and  hold  the 
SRC-131in occupied mode.

 

40005

 

Read Only

 

Bell Status

 

0 = Bell Is Silent 
1 = Bell Is Chiming

 

40006

 

Read / Write

 

Door Station 
Status

 

0 = Normal - No Activity 
1 = “Make Up Room” Active 
2 = “Do Not Disturb” Active

 

40007

 

Read / Write

 

HVAC Status

 

0 = Air Conditioning Off  (1 or 3 Fan Speed) 
1 = Low Speed Ventilation  ( 1 or 3 Fan Speed) 
2 = Med Speed Ventilation (3 Fan Speed Only) 
3 = High Speed Ventilation (3 Fan Speed only) 
4 = Air Conditioning ON  (1 or 3 Fan Speed)

 

40008

 

Read / Write

 

Fan Status

 

3 Fan Speed Mode

 

0 = Low (Fan Auto) 
1 = Med ( Fan Auto) 
2= High (Fan Auto) 
3 = Auto Fan Speed (Fan Auto) 
4 = Low (Fan On) 
5 = Med (Fan On) 
6 = High (Fan On) 
7 = Auto Fan Speed (Fan On) 

1 Fan Speed Mode

 

0 = Fan Auto 
4 = Fan On

 

40009

 

Read / Write

 

User Set Point

 

Deg C =  0.5°C Steps 
Deg F = 1°F Steps 
Value  / 10     ( e.g. 23.5°C = 235)

 

40010 

Read / Write 

Contact 
Reception 
Notification 

0 = Off 
1 = Show Contact Reception on LCD 
SRC-131LCD will flash “Contact Reception” 
on  LCD  and  sound  chime. User  may  accept alert  by  touching 
any button on SRC-131 

40011 

Read Only 

Room 
Temperature 

Value / 10 (e.g. 21.7c = 217) 

40012 

Read / Write 

Temperature 
Display 

0 = Show Room and Set Temperature 
1 = Show Set Temperature Only 

40013 

Read/Write 

C/F Display 

0 = Deg C format 
1 = Deg F format 

40014 

Read / Write 

User Set Point 
High Limit 

5°C to 30°C Range (41°F-86°F) in 1°C/F Steps 
1:1 

40015 

Read / Write 

User Set Point 
Low Limit 

5°C to 30°C Range (41°f-86°F) in 1°C/F Steps 
1:1 

40016 

Read / Write 

Dead Band 

0.5°C to 5.0°C in 0.5°C Steps 
1.0°F to 10.0°F in 1°F Steps 
Value / 10 (e.g. 1.5°C Dead Band = 15) 

Summary of Contents for SRC-131

Page 1: ...SRC 131 Modbus Hotel Room Controller User Manual SyxthSense Ltd 3 Topsham Units Dart Business Park Topsham Exeter Devon EX3 0QH United Kingdom Tel 0844 840 3100 Fax 0844 840 3200 www syxthsense com...

Page 2: ...ies for which SyxthSense Limited has a right to use The contents are copyrighted and must not be communicated in whole or in part to any other party without the prior written approval of SyxthSense Li...

Page 3: ...8 4 9 BELIMO 6 WAY VALVE 8 4 10 2 PIPE MODE 8 5 WIRING EXAMPLES ANCILLARY FUNCTIONS 9 5 1 COMPLETE SYSTEM OVERVIEW 9 5 2 OCCUPANCY DETECTION 9 5 3 WINDOW CONTACT 9 5 4 FAULT INDICATION 10 5 5 DOOR SWI...

Page 4: ...pending on switch and installer menu settings not all segments maybe shown On Off Tap the On Off button to turn the thermostat On or Off and If permitted to select heat only or cool only mode To ensur...

Page 5: ...temperature sensor 3 4 DIP Switch Settings Switch Function On Off Sw1 Indoor Fan Mode 3 Fan Speed 1 Fan Speed Sw2 Equipment Type Heat Pump Heat Cool Sw3 HP Mode Sw2 ON HC Mode Sw2 OFF Rev Valve Heat B...

Page 6: ...or Switch Monitors room door status for occupancy detection see page 11 PIR PIR Movement sensor input for occupancy detection see page 11 The SRC 131 is powered by 24VAC and requires the 24VAC active...

Page 7: ...s actions The SRC 131 displays the relay actions more than the actions of the 0 10V outputs on the LCD In most cases these are very closely matched however as the 0 10v outputs have the capability of...

Page 8: ...this manual As with normal valves the 0 10V heating and cooling span settings in the installer menu scale the heating and cooling outputs Factory default is full heating and full cooling 1 C from set...

Page 9: ...control conferential HVAC systems 2 or 4 pipe fan coils with modulating valves the SRC 131 has the necessary outputs to achieve your control needs 5 2 Occupancy Detection The SRC 131 has sophisticate...

Page 10: ...The text OFF will flash in the display to indicate that the remote door or window switch is holding the SRC 131 in off mode This is done to prevent energy waste by trying to heat or cool an open room...

Page 11: ...ndicates occupancy status 5 12 Doorbell A built in doorbell feature is included with the SRC 131 controller This is normally activated by the optional door station or via Modbus data link In circumsta...

Page 12: ...additional functions within the SRC 131 controller It also permits all modes functions and controls to be remotely supervised and adjusted from a central location if needed Modbus object data can be...

Page 13: ...nu are 1 Ensure that the controller is OFF 2 Tap top left of the LCD then tap top right of the LCD then press and hold the centre of the LCD for 5 seconds 6 1 Navigating Through The Installer Mode Set...

Page 14: ...span 3 speed relays 0 5C 3 0C 1 0F 6 0F 0 1C 0 1F steps Data format Fan span 10 10 0 10V Fan Interval PI 10 300 seconds 10 seconds steps 60 seconds default 11 0 10V Fan direction 0 0 10V slow to fast...

Page 15: ...ps ver 3 3 changed 0 60min 36 Reset Fan 0 Off 1 On 37 Belimo Mode 0 Off 1 On 38 Modbus Address 1 255 39 Baud rate 1 4800bps 2 9600bps default 40 Default Start Temp Version 3 3 0 OFF default 15 35C or...

Page 16: ...Online Store www syxthsense com Copyright 2016 SyxthSense Ltd Enquiries T 0844 840 3100 F 0844 840 3200 SRC 131 Hotel Controller Manual 16 Holding Registers and entering the address simply as 12...

Page 17: ...Low Speed Ventilation 1 or 3 Fan Speed 2 Med Speed Ventilation 3 Fan Speed Only 3 High Speed Ventilation 3 Fan Speed only 4 Air Conditioning ON 1 or 3 Fan Speed 40008 Read Write Fan Status 3 Fan Speed...

Page 18: ...t 0 Off 5 C to 30 C in 0 5 C Steps 41 F to 86 F in 1 F Steps Value 10 e g 17 C Unoccupied Heat 170 40023 Read write Unoccupied Cool Set Point 0 Off 5 C to 30 C in 0 5 C Steps 41 F to 86 F in 1 F Steps...

Page 19: ...7 3v send 1073 40041 Read Write 0 10V Cool Value Value 10 e g 7 3V 73 To write add 10 e g to write 7 3v send 1073 Values below only apply to version 2 hardware only Firmware version 3 40043 Read Write...

Page 20: ...Colours Available Upon Request Display Type STN Touch Panel Relay Rating 30V 1Amp Max 0 10V Output Load 10mA Max Control Range 5 C to 30 C 41 F to 86 F Memory Type Non Volatile Settings Do Not Requir...

Reviews: