Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
External
setpoint
External
setpoint
Not active
Min setp.:
12.0°C
Max setp.:
30.0°C
An external setpoint device can
be connected. The setpoint
device must follow the PT1000
resistance curve. The setting
range can be restricted.
→
Alarm settings
Alarm no(1–100):
1
Run Error Supply
Air
→
Communication
Function Port1
Slave
Function
Expansion unit
Slave
Choose between different
communications
Slave,
Expansion unit, Freq
conv/Press tran,
External display, Exp
and freq conv
or
Exp and
ext display
.
→ Function Port2
Exp and ext
display
PDTxxC-2
Pressure dual transmitter
module.
Expansion unit1
None
Expansion unit2
None
Expansion unit3
PDTxxC-2
Expansion unit4
PDTxxC-2
→
Access rights
→
Log on
Log on
Enter password
xxxx
Actual level:
None
Log on
to service level by
entering a 4-digit code. After
reaching the desired level go
back with “LEFT” arrow (press 2
times) on the control panel.
Standard code from factory to
enter service level is 2222. Back
to operator level: 1111. To enter
Admin level code: 3333.
→
Log off
Log off?
No
Actual
level:None
Log off
from Administrator level
by changing
No
to
Yes
with the
"OK" and "UP/DOWN" buttons
Automatic logoff after 6 minutes
of inactivity.
→
Change
password
Change password
for
level:None
New password
xxxx
Set
a new password for the
level of your choice.
Can only be done once logged
on to the service level.
Topvex FC
Operation and Maintenance Instructions
125918
23