Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Flow control SAF
P-band:
2160.0
m³/h
I-time:
40.0
sec
Min.
output:
0%
Set
P-band, I-time and Min.
output for the supply air fan
when the unit comes configured
as
Flow control
from
factory. Alternatively
Pressure
control
if that configuration is
chosen
Flow control EAF
P-band:
2160.0
m³/h
I-time:
40.0
sec
Min.
output:
0%
Set
P-band, I-time and Min.
output for the Extract air fan
when the unit comes configured
as
Flow control
from
factory. Alternatively
Pressure
control
if that configuration is
chosen
→
Alarm
settings
→
Alarm limits
Set
the alarm limits and allowed
deviations for the different
functions
→
Alarm delays
Set
the alarm delays and
allowed deviation delays for the
different functions
→
Restore alarm
Reset the service alarm (filter
alarm).
Restore factory
settings:
No
Restore user
settings:
No
In this menu, it is possible to
restore all parameters to their
factory settings or to the user
settings they were
saved as
earlier.
Select
Yes
or
No
Save user
settings
No
The current configuration can
be saved in a separate memory
area and can later be restored
using the previous menu,
Restore user settings.
Select
Yes
or
No
Darker gray area, log in
to “Administrator level”
code 3333
→
Configuration
→
Inputs/Outputs
Setup for inputs and outputs.
→
Sensor settings
Setup of sensor types and
control range.