Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Outdoor
comp.Setp.
1
—20°C = 0 Pa
10°C = 0 Pa
Act.
Comp:
0
Pa
Set the SAF pressure
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive
or negative.
Shows the actual pressure
compensation.
Pressure
control EAF
Actual:
Pa
Setp.:
Pa
The actual external pressure
and set point for the extract air
fan.
Only visible if the unit is
configured for "Pressure
control" (VAV).
Pressure control
EAF
Setp 1/1:
200
Pa
Setp 1/2:
100
Pa
Set the external pressure set
point for normal speed (1/1)
and reduced speed (1/2) for the
supply air fan.
Outdoor
comp.Setp.
1
—20°C = 0 Pa
10°C = 0 Pa
Act.
Comp:
0
Pa
Set the EAF pressure
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive
or negative.
Shows the actual pressure
compensation.
Extra flow EAF
Actual:
m³/h
Shows the extract air flow
→
Time settings
→
Time/Date
Set correct time and date.
Set 00:00 - 24:00 for continuous
running. Setting 00:00 - 00:00
inactivates the period (stops the
unit). Normal speed overrides
Reduced speed i.e. Normal
speed 07:00 - 16:00 and
Reduced speed 00:00 - 24:00
runs the unit on Normal speed
07:00 - 16:00 and Reduced
speed the rest of the day.
Topvex FC
Operation and Maintenance Instructions
125918
13