Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
→
Manual/Auto
In this menu the running mode
of all the configured output
signals and a number of control
functions can be manually
controlled.
The supply air controller's output
signal can be manually set
(
Manual/Auto
) to any value
between 0 and 100%. The
temperature output signals will
change accordingly if they are
in Auto mode. It is also possible
to manually control each of
the temperature output signals
individually.
Since leaving any of the
outputs in manual control will
disrupt the normal control,
an alarm will be generated as
soon as any output is set to a
manual mode.
Supply temp.
contr.
Auto
Manual set:
0.0
Set the supply air temperature
controller to
Auto
,
Manual
or
Off
.
Set the output signal between
0-100%.
The outputs Y1, Y2 and Y3, if in
Auto-mode, will follow the signal
according to the set split values.
SAF: Auto
Manual set:
0.0
Set the output signal for SAF
(supply air fan) to:
Auto
,
Manual
,
1/2–speed
or
1/1–speed
.
EAF: Auto
Manual set:
0.0
Set the output signal for EAF
(extract air fan) to:
Auto
,
Manual
,
1/2–speed
or
1/1–speed
.
Heating
Auto
Manual set:
100.0
Set the heating to
Auto
,
Manual
or
Off
.
Set the manual output 0-100%.
Exchanger
Auto
Manual set:
0.0
Set the exchanger rotor control
to
Auto
,
Manual
or
Off
Set the manual output 0-100%
Topvex FC
Operation and Maintenance Instructions
125918
15
Systemair Sverige AB